Plan Review Notes
Plan Review Notes For Permit 05030779
Permit Number 05030779
Review Stop E
Sequence Number 10
Notes
Date Text
2006-08-01 00:00:00** UNSAT **
  
 1) NOTE: PLEASE SEE STEAM GEN WAS ADDED
 TO PANEL SCHEDULE, HOWEVER THIS DOES NOT
 SEEM TO HAVE BEEN ADDED TO LOAD
 CALCULATIONS.
 PLEASE REFIGURE LOAD CALCULATIONS.
  
 220, 215.5 ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  