| 2005-04-13 00:00:00 | **** NOTES **** |
| | |
| | PLEASE SEE PLANS AREIN VERY GOOD |
| | SHAPE, HOWEVER PLANS ARE COMING BACK FOR |
| | ZONING COMMENTS. PLEASE SEE THE BELOW |
| | MINOR CHANGES TO ADJUST AT THIS TIME. |
| | |
| | 1)NOTE: PLEASE SEE RISER: NOTE ON METER |
| | INDICATES A METER/MAIN COMBO PANEL, YET, |
| | RISER SHOWS METER AND THEN FUSED DISC |
| | BEFORE FEEDING TWO MLO FEED THROUGH |
| | PANELS. |
| | PLEASE CLARIFY IF INDEED METER MAIN |
| | COMBO? IF SO, PLEASE INCLUDE EQUIPMENT |
| | GROUNDING FROM METER MAIN TO FUSED |
| | DISCONNECT. 250.110,250.24,250.122 |
| | HOWEVER, THIS APPEARS TO BE A MISPRINT |
| | AND IF INDEED THIS IS ONLY A METER |
| | FEEDING A FUSED DISCONNETC, PLEASE ONLY |
| | REMOVE METER/MAIN NOTE ON METER. |
| | |
| | 2)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 |
| | 8-1.4.2.8-1.4.1.6.2 |
| | COMMON TEXT NOTE, HOWEVER PLEASE SEE |
| | NOTES BELOW. |
| | |
| | PLEASE SEE MISSING SD;S REQUIRED OUTSIDE |
| | MASTER BEDRM, BEDRM #'S 2,3,4 AND 5. |
| | SD MAY BE PLACED OUTSIDE 2,3 AND 4 TO |
| | MEET "OUTSIDE". ONE ADDITIONAL SD NEEDS |
| | TO BE OUTSIDE BEDRM #5. |
| | |
| | PLEASE SEE SD FOR INSIDE BEDRM #5 NEEDS |
| | TO BE "INSIDE" BEDRM AS HEADER IS SHOWN |
| | AT DOORWAY. |
| | |
| | PLEASE SEE SD MISSING OUTSIDE MASTER |
| | BEDRM, PLEASE ALSO SEE SD "INSIDE" |
| | MASTER BEDRM IS REQUIRED TO BE WITH/IN |
| | 3' OF PEAK. NFPA-72 2-3.4.7 |
| | |
| | PLEASE SEE SD'S SHOWN INSIDE AND OUTSIDE |
| | LAUNDRY RM? THESE ARE NOT REQUIRED, BUT |
| | HOWEVER THESE ARE PERMITTED. |
| | THE SD OUTSIDE LAUNDRY RM/BATH MUST BE A |
| | MIN OF 3' FROM BATH DOOR PER NFPA-72 |
| | 8-1.4.2 THIS IS ONLY A NOTE: |
| | |
| | PLEASE SEE SD LOCATIONS ARE REDLINED ON |
| | ONE SET OF PLANS FOR LOCATIONS OF ABOVE |
| | NOTES. |
| | |
| | 3)NOTE: PLEASE VERIFY OF GAS STOVE AND |
| | GAS WH IS A 220V CIRCUIT. THIS IS ONLY A |
| | NOTE AND NO CHANGE IS NEEDED. |
| | |
| | IF THERE ARE ANY QUESTIONS, PLEASE DO |
| | NOT HESITATE TO CALLTO GO OVER ANY |
| | COMMENTS. |
| | PLEASE SUBMIT THE ABOVE FOR REVIEW. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |