Plan Review Notes
Plan Review Notes For Permit 05030779
Permit Number 05030779
Review Stop E
Sequence Number 1
Notes
Date Text
2005-04-13 00:00:00**** NOTES ****
  
 PLEASE SEE PLANS AREIN VERY GOOD
 SHAPE, HOWEVER PLANS ARE COMING BACK FOR
 ZONING COMMENTS. PLEASE SEE THE BELOW
 MINOR CHANGES TO ADJUST AT THIS TIME.
  
 1)NOTE: PLEASE SEE RISER: NOTE ON METER
 INDICATES A METER/MAIN COMBO PANEL, YET,
 RISER SHOWS METER AND THEN FUSED DISC
 BEFORE FEEDING TWO MLO FEED THROUGH
 PANELS.
 PLEASE CLARIFY IF INDEED METER MAIN
 COMBO? IF SO, PLEASE INCLUDE EQUIPMENT
 GROUNDING FROM METER MAIN TO FUSED
 DISCONNECT. 250.110,250.24,250.122
 HOWEVER, THIS APPEARS TO BE A MISPRINT
 AND IF INDEED THIS IS ONLY A METER
 FEEDING A FUSED DISCONNETC, PLEASE ONLY
 REMOVE METER/MAIN NOTE ON METER.
  
 2)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72
 8-1.4.2.8-1.4.1.6.2
 COMMON TEXT NOTE, HOWEVER PLEASE SEE
 NOTES BELOW.
  
 PLEASE SEE MISSING SD;S REQUIRED OUTSIDE
 MASTER BEDRM, BEDRM #'S 2,3,4 AND 5.
 SD MAY BE PLACED OUTSIDE 2,3 AND 4 TO
 MEET "OUTSIDE". ONE ADDITIONAL SD NEEDS
 TO BE OUTSIDE BEDRM #5.
  
 PLEASE SEE SD FOR INSIDE BEDRM #5 NEEDS
 TO BE "INSIDE" BEDRM AS HEADER IS SHOWN
 AT DOORWAY.
  
 PLEASE SEE SD MISSING OUTSIDE MASTER
 BEDRM, PLEASE ALSO SEE SD "INSIDE"
 MASTER BEDRM IS REQUIRED TO BE WITH/IN
 3' OF PEAK. NFPA-72 2-3.4.7
  
 PLEASE SEE SD'S SHOWN INSIDE AND OUTSIDE
 LAUNDRY RM? THESE ARE NOT REQUIRED, BUT
 HOWEVER THESE ARE PERMITTED.
 THE SD OUTSIDE LAUNDRY RM/BATH MUST BE A
 MIN OF 3' FROM BATH DOOR PER NFPA-72
 8-1.4.2 THIS IS ONLY A NOTE:
  
 PLEASE SEE SD LOCATIONS ARE REDLINED ON
 ONE SET OF PLANS FOR LOCATIONS OF ABOVE
 NOTES.
  
 3)NOTE: PLEASE VERIFY OF GAS STOVE AND
 GAS WH IS A 220V CIRCUIT. THIS IS ONLY A
 NOTE AND NO CHANGE IS NEEDED.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE TO CALLTO GO OVER ANY
 COMMENTS.
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  