| Plan Review Notes For Permit 05030668 |
| Permit Number |
05030668 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-05-16 00:00:00 | ***** UNSAT ******* | | | | | | PLEASE SEE THESE ARE NEW AS THIS | | | INFORMATION WAS NOT SUBMITTED ON | | | ORIGINAL REVIEW. | | | | | | 1)NOTE: PLEASE SEE PANEL SCHEDULE. | | | PLEASE SEE NUMEROUS ITEMS WHICH NEED | | | CORRECTING. PLEASE SEE 20A OCP ON #14 | | | AWG. PLEASE SEE 15A FOR SMALL APPL | | | CIRCUITS. PLEASE SEE #14 SHOWNFOR | | | BATHS. PLEASE SEE CIRCUIT #23, NO ARC | | | FAULT PROTECTION NOTED. | | | PLEASE SEE | | | 210.52D,210-52,210.11C1,210.11C3,220.16, | | | 210.12 ETC. | | | PLEASE SEE ONE SET OF PLANS HAVE MANY OF | | | THESE ITEMS REDLINED FOR AREAS OF NOTES. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | |
|