| Date |
Text |
| 2005-03-17 00:00:00 | ********* UNSAT ********** |
| | |
| | 1)NOTE: PLEASE SEE FBC 104.2.1, ALL |
| | PLANS ARE REQUIRED TO HAVE THE PRINTED |
| | NAME AND SIGNATURE OF PERSON RESPONSIBLE |
| | FOR PLANS. |
| | THIS IS REQUIRED ON ALL PLANS AND FOR |
| | ALL SHEETS WHEATHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S). |
| | |
| | 2)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED |
| | PANEL SCHEDULE. |
| | |
| | 3)NOTE: PLEASE SEE FBC CHAPTER 34 FOR |
| | RENOVATIONS TO EXISTING DWELLINGS. |
| | PLEASE SHOW LOCATIONS OF EXISTING SD'S |
| | REQUIRED INSIDE AND OUTSIDE BEDRMS OR |
| | NEW REQUIRED TO BE INSTALLED. |
| | PLEASE SHOW LOCATIONS OF EITHER EXISTING |
| | RECEPTS PER 210.52 OR NEW . |
| | |
| | 4)NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210.8A-6 |
| | |
| | 5)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | THIS IS A COMMON TEXT NOTE: PLEASE SEE |
| | NOTE #3. |
| | |
| | 6)NOTE: PLEASE SEE RECEPTS SERVING |
| | KITCHEN COUNTERSPACE TO MEET 210.52C- |
| | SEC'S 1,2,3,4 AND 5 |
| | |
| | 7)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS |
| | ON PLANS. |
| | |
| | 8)NOTE: PLEASE SHOW CONTROL FOR REQUIRED |
| | EGRESS LIGHTING PER 210.70, LS 101 5-8 |
| | PLEASE SEE FANS NOT SHOWN AS FANS LTS, |
| | SYSMBOL FOR RECESSED LTS TO CORRELATE |
| | WITH SYMBOL SCHEDULE. |
| | |
| | 9)NOTE: PLEASE CLARIFY IF PANEL IS NEW |
| | OR EXSITNG? PLEASE CLARIFY EXISTING FEED |
| | TO PANEL, OCP? CONDUCTORS? |
| | 215.5, 240.4,310.16 |
| | |
| | 10)NOTE: PLEASE CORRELATE LOAD CALCS |
| | WITH LOAD ON PANEL SCHEDULE FOR AHU |
| | HEAT. |
| | PLEASE SEE ONE SHOWS 10KW AND THE OTHER |
| | SHOWS 7.5KW |
| | |
| | 11)NOTE: PLEASE SEE 220.19 FOR MIN KW |
| | RATING TO BE FIGURED FOR RANGES. |
| | PLEASE SEE ONLY 3KW SHOWN ON A 50A |
| | CIRCUIT? |
| | PLEASE ALSO SEE WATER HEATER SHOWN AT |
| | 1.5KW? |
| | |
| | 12)NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | |
| | PLEASE SEE SOM OF THE ABOVE ITEMS ARE |
| | REDLINED ON ONE SET OF PLANS FOR |
| | REFERENCE OF NOTES ABOVE. |
| | |
| | PLEASE REMOVE ANY OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO TWO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | PLEASE SUBMIT ONE COPY OF OLD SHEETS FOR |
| | REFERENCE ONLY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |