Plan Review Notes
Plan Review Notes For Permit 05030668
Permit Number 05030668
Review Stop E
Sequence Number 1
Notes
Date Text
2005-03-17 00:00:00********* UNSAT **********
  
 1)NOTE: PLEASE SEE FBC 104.2.1, ALL
 PLANS ARE REQUIRED TO HAVE THE PRINTED
 NAME AND SIGNATURE OF PERSON RESPONSIBLE
 FOR PLANS.
 THIS IS REQUIRED ON ALL PLANS AND FOR
 ALL SHEETS WHEATHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 2)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE.
  
 3)NOTE: PLEASE SEE FBC CHAPTER 34 FOR
 RENOVATIONS TO EXISTING DWELLINGS.
 PLEASE SHOW LOCATIONS OF EXISTING SD'S
 REQUIRED INSIDE AND OUTSIDE BEDRMS OR
 NEW REQUIRED TO BE INSTALLED.
 PLEASE SHOW LOCATIONS OF EITHER EXISTING
 RECEPTS PER 210.52 OR NEW .
  
 4)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 5)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 THIS IS A COMMON TEXT NOTE: PLEASE SEE
 NOTE #3.
  
 6)NOTE: PLEASE SEE RECEPTS SERVING
 KITCHEN COUNTERSPACE TO MEET 210.52C-
 SEC'S 1,2,3,4 AND 5
  
 7)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS
 ON PLANS.
  
 8)NOTE: PLEASE SHOW CONTROL FOR REQUIRED
 EGRESS LIGHTING PER 210.70, LS 101 5-8
 PLEASE SEE FANS NOT SHOWN AS FANS LTS,
 SYSMBOL FOR RECESSED LTS TO CORRELATE
 WITH SYMBOL SCHEDULE.
  
 9)NOTE: PLEASE CLARIFY IF PANEL IS NEW
 OR EXSITNG? PLEASE CLARIFY EXISTING FEED
 TO PANEL, OCP? CONDUCTORS?
 215.5, 240.4,310.16
  
 10)NOTE: PLEASE CORRELATE LOAD CALCS
 WITH LOAD ON PANEL SCHEDULE FOR AHU
 HEAT.
 PLEASE SEE ONE SHOWS 10KW AND THE OTHER
 SHOWS 7.5KW
  
 11)NOTE: PLEASE SEE 220.19 FOR MIN KW
 RATING TO BE FIGURED FOR RANGES.
 PLEASE SEE ONLY 3KW SHOWN ON A 50A
 CIRCUIT?
 PLEASE ALSO SEE WATER HEATER SHOWN AT
 1.5KW?
  
 12)NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 PLEASE SEE SOM OF THE ABOVE ITEMS ARE
 REDLINED ON ONE SET OF PLANS FOR
 REFERENCE OF NOTES ABOVE.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONE COPY OF OLD SHEETS FOR
 REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  
  