| 2005-06-04 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | CITY CODE |
| | |
| | A. FROM PREVIOUS REVIEW: |
| | |
| | 2) ALL ARCHITECTURAL SHEETS, THE PRINTED |
| | NAME AND CERTIFICATE OF AUTHORIZATION IS |
| | REQUIRED ON EACH SHEET PER FAC |
| | 61G1-16.004(2) & (6) AND FS 481.219 & |
| | 481.2055. - RESPONSE NOTED, BUT COMMENT |
| | NOT ADDRESSED. |
| | 3) ALL SHEETS WITH CRAVEN THOMPSON & |
| | ASSOCIATES, (CIVIL), REQUIRE A |
| | CERTIFICATE OF AUTHORIZATION NUMBER IN |
| | THE TITLE BLOCK. FAC 61G15-23.002(2) & |
| | FS 471.025. - RESPONSE NOTED, BUT |
| | COMMENT NOT ADDRESSED. |
| | 5) A DRINKING FOUNTAIN IS REQUIRED PER |
| | TABLE 403.1. - RESPONSE NOTED AS "A |
| | BOTTLE OF WATER", BUT A BOTTLED WATER |
| | COOLER ARI-1010 COMPLIANT IS REQUIRED IF |
| | A DRINKING FOUNTAIN IS NOT INSTALLED. |
| | SUBMIT MANUF. SPECIFICATION SHEETS THE |
| | BOTTLED WATER COOLER. SECTION 410.1 |
| | 6) SHT A5.0 SHEET IS "NOT" SIGNED, |
| | SEALED, OR DATED AS REQUIRED BY FAC |
| | 61G1-16.004(5) AND FS 481.2055. - NO |
| | RESPONSE BECAUSE I FORGOT TO ADD "NOT". |
| | 7) SHT A6.0 DETAIL #1 PER THE BUILDING |
| | OFFICIAL NO CABINET DOORS ALLOWED IN THE |
| | CLEAR FLOOR SPACE), AND FAUCETS |
| | 11-4.24.7. REQUIRED ON PLANS |
| | TO SHOW COMPLIANCE. - RESPONSE NOTED, |
| | BUT NOT ALL SECTIONS ADDRESSED. |
| | 8) ALL FS SHEETS, A CERTIFICATE OF |
| | AUTHORIZATION IS REQUIRED ON THE TITLE |
| | BLOCK ON EACH SHEET. ALSO THE SEAL AND |
| | SIGNATURE SHALL BE DATED WHEN SEAL AND |
| | SIGNATURE ARE AFFIXED TO PLANS. FAC |
| | 61G15-23.002(2) & FS 471.2055.RESPONSE |
| | NOTED, BUT IF THE ENGINEER WORKS FOR |
| | BLYMYER ENGINEERING INC. A CERTIFICATE |
| | OF AUTHORIZATION IS REQUIRED. IF THE |
| | ENGINEER DOES NOT WORK FOR BLYMER |
| | ENGINEERING INC., HE MUST LEGIBLY |
| | INDICATE HIS ADDRESS ON EACH SHEET. |
| | **************NEW COMMENTS************** |
| | 1B. SHT P3.1 SANITARY RISER DIAGRAM. A |
| | FUNNEL FLOOR DRAIN IS NOT AN APPROVED |
| | INDIRECT WASTE RECEPTOR. PER SECTIONS |
| | 802.3, AND 802.3.2 EITHER A FLOOR SINK |
| | OR A HUB DRAIN IS REQUIRED. |
| | 2B. SHT P3.1 SANITARY RISER DIAGRAM. THE |
| | BREAK ROOM SINK SHALL NOT DRAIN THROUGH |
| | THE HORIZONTAL WET VENT OF THE BATHROOM |
| | FIXTRUES. THE SINK SHALL DISCHARGE |
| | DOWNSTREAM OF THE BATHROOM FIXTURES. |
| | SECTION 909.1 |
| | |