| 2005-05-16 00:00:00 | ********** UNSAT 2ND REVIEW *********** |
| | |
| | PLANS SUBMITTED FOR "PLAN REVIEW" ONLY |
| | AND NOT SUBMITTED FOR PERMIT. |
| | |
| | 1)NOTE: PLEASE SEE NOTE #1 FROM PREVIOUS |
| | REVIEW. |
| | PLEASE SEE MISSING INFORMATION ON TITLE |
| | BLOCKS FOR P,M,E, ARCH SHEETS AND FS |
| | SHEETS ALSO. PLEASE SEE ANY OTHER SHEETS |
| | WHICH POSSIBLY MAY ALSO HAVE MISSING |
| | REQUIRED LICENSE INFORMATION. |
| | PLEASE SEE FAC 61G1-16.004, FAC |
| | 61G15-23.002. |
| | REQUIRED PER FS 481.219, 471.023 |
| | THIS INFORMATION IS REQUIRED FOR ALL |
| | SHEETS AND FOR ALL TRADES WHEATHER OR |
| | NOT COMMENT IS MADE BY OTHER |
| | REVIEWER(S). |
| | PLEASE SEE THIS WAS NOTED ON PREVIOSU |
| | REVIEW AND RESPONSE LTR MENTIONS: "PLANS |
| | CORRECTED TO INCLUDE THE PRINTED NAME |
| | AND SIGNATURE OF PERSON RESPONSIBLE FOR |
| | PLANS". THIS IS REQUIRED ALSO UNDER FBC |
| | 104.2.1, HOWEVER THIS IS NOT THE ONLY |
| | ITEM WHICH WAS NOTED. |
| | |
| | 2)NOTE: PLEASE PORVIDE WIND LOADING FOR |
| | LIGHT POLES AND FIXTURES PER FBC 140 |
| | MPH. |
| | THIS IS REQUIRED AT THIS TIME IF SITE |
| | LIGHTING IS UNDER THIS PERMIT. |
| | |
| | 3)NOTE: PLEASE SEE 250.6,250.24 |
| | EQUIPMENT GROUNDING CONDUCTORS SHALL NOT |
| | BE INSTALLED UNTIL AFTER THE FIRST MEANS |
| | OF DISCONNECT. |
| | |
| | 4)NOTE: PLEASE CORRELATE FS PLANS WITH |
| | E-SHEETS. |
| | PLEASE SEE FS PANEL INDICATE BEING FED |
| | FROM PANEL LA?? |
| | PLEASE SEE PANELS SHOWN ON FS SHEETS DO |
| | NOT CORRELATE WITH E-SHEETS?? |
| | SC, DHI ETC? |
| | 215.5 |
| | |
| | 5)NOTE: PLEASE SEE DISCONNECTING MEANS |
| | FOR DETACHED STRUCTURES PER |
| | 225.31-225.36 FUEL CANOPY |
| | |
| | 6)NOTE: PLEASE SEE 250.32 FOR GROUNDING |
| | ELECTRODE CONNECTION AT DETACHED |
| | STRUCTURES. |
| | |
| | 7)NOTE: PLEASE PROVIDE POSSIBLE CLASS |
| | LOCATION FOR SERVICE BAY AREAS. |
| | PLEASE SEE POSSIBLE EXEMPTIONS IN NEC |
| | 511. |
| | PLEASE PROVIDE NOTES ON PLANS FOR |
| | USEAGE/CLASS. SEE POSSIBLE NOTES FROM |
| | OTHER TRADES. |
| | PLEASE SEE POSSIBLE AIR CHANGES. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | PLEASE SUBMIT ONLY ONE SET OF OLD/VOIDED |
| | SHEETS FOR REFERENCE ONLY. |
| | |
| | PLEASE SEE POSSIBLE COMMMENTS FROM OTHER |
| | TRADES WHICH MAY HAVE AN AFFECT ON |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |