Text |
| 2005-03-25 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | CITY CODE |
| | |
| | 1) SHT PRIOR TO SHT C-3, ALL INFORMATION |
| | DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME |
| | AND SIGNATURE OF THE PERSON RESPONSIBLE |
| | FOR THE DESIGN. SECTION 104.2.1. |
| | 2) ALL ARCHITECTURAL SHEETS, THE PRINTED |
| | NAME AND CERTIFICATE OF AUTHORIZATION IS |
| | REQUIRED ON EACH SHEET PER FAC |
| | 61G1-16.004(2) & (6) AND FS 481.219 & |
| | 481.2055. |
| | 3) ALL SHEETS WITH CRAVEN THOMPSON & |
| | ASSOCIATES, (CIVIL), REQUIRE A |
| | CERTIFICATE OF AUTHORIZATION NUMBER IN |
| | THE TITLE BLOCK. FAC 61G15-23.002(2) & |
| | FS 471.025. |
| | 4) SHT C-10 CALL FOR A SAND/OIL |
| | INTECEPTOR. THIS SHALL BE SIZED BY |
| | RONDEY COMPO, ENVIRONMENTAL COMPLIANCE. |
| | WASTE ORDINANCE 2938-96. CONTACT MR. |
| | COMPO AT (561) 837-4074 OR E-MAIL |
| | ADDRESS [email protected]. |
| | 5) A DRINKING FOUNTAIN IS REQUIRED PER |
| | TABLE 403.1. |
| | 6) SHT A5.0 SHEET IS SIGNED/SEALED/DATED |
| | AS REQUIRED BY FAC 61G1-16.004(5) AND |
| | FS 481.2055. |
| | 7) SHT A6.0 DETAIL #1 SHOW THE HEIGHT |
| | 11-4.24.2, KNEE CLEARANCE 11-4.24.3, |
| | SINK DEPTH 11-4.24.4, CLEAR FLOOR SPACE |
| | 11-4.24.5 (FORWARD APPROACH EXTENDING |
| | MAXIMUM 19" UNDERNEATH THE SINK REQD, |
| | AND PER THE BUILDING OFFICIAL NO CABINET |
| | DOORS ALLOWED IN THE CLEAR FLOOR SPACE), |
| | EXPOSED PIPES AND SURFACES 11-4.24.6, |
| | AND FAUCETS 11-4.24.7. REQUIRED ON PLANS |
| | TO SHOW COMPLIANCE. |
| | 8) ALL FS SHEETS, A CERTIFICATE OF |
| | AUTHORIZATION IS REQUIRED ON THE TITLE |
| | BLOCK ON EACH SHEET. ALSO THE SEAL AND |
| | SIGNATURE SHALL BE DATED WHEN SEAL AND |
| | SIGNATURE ARE AFFIXED TO PLANS. FAC |
| | 61G15-23.002(2) & FS 471.2055. |
| | 9) SUBMIT A SANITARY RISER ISOMETRIC |
| | THAT REFLECTS THE FLOOR PLAN. SHOW ALL |
| | PIPE SIZES, REQUIRED TRAPS, VENTS, AND |
| | CLEANOUTS. SECTION 104.3.1.1. |
| | 10) SUBMIT A WATER RISER ISOMETRIC. SHOW |
| | ALL PIPE SIZES, VALVES, REQUIRED WATER |
| | HAMMER ARRESTORS LOCATED NEAR THE |
| | FIXTURES IN AN "EFFECTIVE RANGE" PER |
| | PDI-WH 201, REQUIRED BACKFLOWS ECT. |
| | SECTION 104.2.1.1. |
| | 11) WATER SUPPLY TO THE CAR WASH SHALL |
| | HAVE AN RPZ BACKFLOW PROTECTION. SECTION |
| | 608.13.2. |
| | 12) SUBMIT A ROOF PLAN SHOWING ALL |
| | PRIMARY AND SECONDARY ROOF DRAINS. |
| | INDICATE THE SQUARE FOOTAGE OF THE ROOF |
| | AND THE SQUARE FOOTAGE DRAINING INTO |
| | EACH DRAIN. SUBMIT CALCULATIONS FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS. |
| | INCLUDE 1/2 AREA OF ALL VERTICAL WALLS |
| | INCLUDING PARAPETS IN CALCULATIONS. |
| | SECTIONS 1106 & 1107 AND ALL SUBSECTIONS |
| | SUBMIT A DETAIL FOR SCUPPERS IF USED FOR |
| | SECONDARY ROOF DRAINS SHOWING HEIGHT & |
| | WIDTH. SUBMIT STORM DRAIN ISOMETRIC AND |
| | STORM RISER DIAGRAMS SHOWING ALL PIPE |
| | SIZES AND SQUARE FOOTAGE AS IT |
| | ACCUMULATES IN THE SYSTEM. SECTION |
| | 104.2.1. |
| | 13) PLANS ARE INCOMPLETE AT THIS REVIEW |
| | AND MORE COMMENTS MAY BE ADD ON THE NEXT |
| | REVIEW. SECTION 104.2.1. |
| | |