| 2005-04-11 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05030626 |
| | ADD: 2505 BRISTOL DRIVE |
| | CONT:PLAN REVIEW |
| | TEL: (561)684-5449#209 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1)FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | DISCREPANCY BETWEEN THE VICINITY MAP |
| | SHEET A0.1 INDICATING THE SITE AND THE |
| | PLAT MAP. |
| | |
| | 2)PROVIDE NOC RECORDED WITH THE CLERK OF |
| | COURT BEFORE A PERMIT CAN BE ISSUED. |
| | ***NOTE, ONCE THE NOTICE OF COMMENCEMENT |
| | IS RECORDED WORK MUST BE COMMENCED OR BE |
| | RE-RECORDED.**** |
| | |
| | 3) THE STRUCTURAL PLANS S-4 INDICATE THE |
| | USE OF MANUFACTURED METAL BUILDINGS, NO |
| | DRAWINGS WERE SUPPLIED.PLANS ARE TO |
| | INDICATE WIND ZONE AND DESIGN CRIERIA. |
| | |
| | 4)FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) ROLL UP DOORS |
| | B) EXTERIOR SWING DOORS, SOLID & |
| | LOUVERED |
| | C) WINDOWS |
| | D) STORM SHUTTERS |
| | E) ROOFING ASSEMBLIES |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 5) INDICATE THE PRESSURES FOR THE |
| | WINDOWS AND DOORS OF THE ENCLOSED |
| | STURURE? |
| | |
| | 6) SEE SHEET A6.0 DETAIL# 1 BREAKROOM |
| | ELEVATIONS INDICATE SECTION# 7 FOR |
| | HEIGHT DETAILS.PLEASE MAKE CORRETIONS. |
| | 11-4.24.2 SINKS, HEIGHT. SINKS SHALL |
| | BE MOUNTED WITH THE COUNTER NO HIGHER |
| | THAN 34" ABOVE THE FINISH FLOOR. |
| | 11-4.24.3 KNEE CLEARENCE THAT IS AT |
| | LEAST 27" HIGH 30" WIDE, AND 19" DEEP |
| | SHALL BE PROVIDED UNDERNEATH SINKS. |
| | |
| | 7) FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, SHEET |
| | A2.0 INDICATES FLOOR PLAN NOTES, PLANS |
| | INDICATE VARIOUS NUMBERED DETAILS BUT NO |
| | NOTES FOLLOW, EXAMPLE 2-4 OR 6-7? |
| | |
| | 8)MECH TABLE 403.4.2 PUBLIC SPACES, |
| | TOLIET ROOMS/ 50 CFM/ WATER CLOSET |
| | FOOTNOTE "B" EXHAUST REQUIRED & |
| | RECIRCULATION OF AIR IS PROHIBITED. |
| | |
| | 9) FL BLD CODE 1804.2.2 QUESTIONABLE |
| | SOILS, WHERE THE BEARING CAPACITY IS |
| | NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| | WHERE THE BEARING CAPACITY OF THE SOIL |
| | IS NOT DEFINITLY KNOWN OR IS IN QUESTION |
| | THE BUILDING OFFICIAL MAY REQUIRE EXPLOR |
| | ATIONS, TEST OR OTHER ADEQUATE PROOF AS |
| | TO THE PERMISSIBLE SAFE BEARING |
| | CAPACITY. REQUIRED TEST AND RECOMMENDA- |
| | TIONS SUBMITTED TO VERIFY BEARING CAPA- |
| | CITY SHALL BE CERTIFIED BY A GEOTECH- |
| | NICALREPORT FROM A DESIGN PROFESSIONAL |
| | PROPERLY LICENSED IN THE STATE OF |
| | FLORIDA. |
| | |
| | 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |
| | |
| | |