2005-05-16 00:00:00DENIED:PLAN CHECK ONLY
 1.PLAN SHEET M-1, FLEX DUCT
 PENETRATING RATED PARTITION AT THE
 CORRIDOR & CONFERENCE ROOM SHALL COMPLY
 WITH 2001 FBC/M 607.1.3 #3 ITEMS 1
 THROUGH 4.ALSO 10" FLEXD PENETRATING
 BOTH CONFERENCE ROOMS MISSING A FIRE
 DAMPER.PLEASE NOTE FLEX DUCT SHALL NOT
 PENETRATE RATED WALL OR PARTITIONS PER
 2001 FBC/M 603.5.5.
  
 2.PLAN SHEET M-2, DUCTS PENETRATING
 JURY ROOM SHALL COMPY WITH 2001 FBC/M
 607.1.3 #3 ITEMS 1 THROUGH 4.
  
 3.M-2, 6" SUPPLY DUCT FROM THE COPY
 ROOM INTO THE COORIDOR (RATED WALL).
  
 4.PROVIDE FIRE DAMPERS AT PENTRATION
 THROUGH THE EXTERIOR WALL FOR COMPLIANCE
 WTIH 2001 FBC/M607.1.2 & 607.4
  
 5.PROVIDE ENERGY CALCULATIONS IN
 ACCORDANCE WITH 2001 FBC CHAPTER 13 SUB
 CHAPTER 400.
  