| Plan Review Notes For Permit 05030625 |
| Permit Number |
05030625 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-05-16 00:00:00 | DENIED:PLAN CHECK ONLY | | | 1.PLAN SHEET M-1, FLEX DUCT | | | PENETRATING RATED PARTITION AT THE | | | CORRIDOR & CONFERENCE ROOM SHALL COMPLY | | | WITH 2001 FBC/M 607.1.3 #3 ITEMS 1 | | | THROUGH 4.ALSO 10" FLEXD PENETRATING | | | BOTH CONFERENCE ROOMS MISSING A FIRE | | | DAMPER.PLEASE NOTE FLEX DUCT SHALL NOT | | | PENETRATE RATED WALL OR PARTITIONS PER | | | 2001 FBC/M 603.5.5. | | | | | | 2.PLAN SHEET M-2, DUCTS PENETRATING | | | JURY ROOM SHALL COMPY WITH 2001 FBC/M | | | 607.1.3 #3 ITEMS 1 THROUGH 4. | | | | | | 3.M-2, 6" SUPPLY DUCT FROM THE COPY | | | ROOM INTO THE COORIDOR (RATED WALL). | | | | | | 4.PROVIDE FIRE DAMPERS AT PENTRATION | | | THROUGH THE EXTERIOR WALL FOR COMPLIANCE | | | WTIH 2001 FBC/M607.1.2 & 607.4 | | | | | | 5.PROVIDE ENERGY CALCULATIONS IN | | | ACCORDANCE WITH 2001 FBC CHAPTER 13 SUB | | | CHAPTER 400. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|