Plan Review Notes
Plan Review Notes For Permit 05030625
Permit Number 05030625
Review Stop B
Sequence Number 2
Notes
Date Text
2005-05-24 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 1.)THE ONLY CHANGE MADE TO A1 THROUGH
 A4 WAS TO ADD THE DOOR LEGEND.ALL
 OTHER COMMENTS NOT ADDRESSED ON THE PLAN
 WITH THE EXCEPTION OF ADDING BUILDING
 TYPE ONTO THE COVER PAGE.THIS CHANGE
 WAS NOT CLOUDED AND NUMBERED.
  
 2.)THERE ARE SOME HAND DRAWN NOTES ON
 ONE OF THE PLANS.TWO IDENTICAL SETS
 ARE TO BE SUBMITTED.THE HAND DRAWN
 CHANGES WERE NOT INITIALED.
  
 3.)SOME COMMENTS WERE ADDRESSED
 THROUGH A TRANSMITTAL LETTER.THE PLANS
 ARE TO SHOW CODE COMPLIANCE.THESE
 ISSUES SHOULD BE ADDRESSED ON THE PLAN.
  
 4.)FOR THE FIRE RATED WALL (PREVIOUS
 LIST ITEM 1D) AND JOINT SYSTEMS
 (PREVIOUS LIST ITEM 1F) PROVIDE AN
 ASSEMBLY OR GYPSUM LISTING AS REQUESTED
 BY PREVIOUS REVIEWER.NO DETAILS WERE
 PROVIDED.
  
 5.)THE PERMIT APPLICATION IS NOT IN
 THE PACKAGE.
  
 6.)THE TRANSMITTAL SHEET STATES THAT
 SHEET M2 WAS CHANGED.NOTHING IS
 CLOUDED AND THERE ISN'T A REVISION
 NUMBER.ALL REVISIONS ARE TO BE CLEARLY
 INDICATED.
  
 7.)SHEET M2 SHOWS 2 12X12 GRILLES IN
 THE STAIRWAY.SEE PREVIOUS LIST ITEM
 1E, FBC705.2.3.5 IN REGARDS TO OPENINGS
 IN THE STAIRWELL SHAFT.
  
 8.)SEE ATTACHED FS553.80(2)(B).
  
 WHEN RESUBMITTING, REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND SUBMIT OLD SHEETS
 SEPARATELY.A TRANSMITTAL LETTER WILL
 HELP EXPEDITE PLAN REVIEW.