Plan Review Notes
Plan Review Notes For Permit 05030625
Permit Number 05030625
Review Stop E
Sequence Number 1
Notes
Date Text
2005-03-22 00:00:00***** UNSAT *****
  
  
 PLEASE SEE PLANS ARE ONLY IN FOR "PLAN
 REVIEW" AT THIS TIME AND NOT FOR PERMIT.
  
 1)NOTE: PLEASE SEE MISSING INFORMATION
 ON TITLE BLOCK AS REQUIRED UNDER FAC
 61G15-23.002.
 PLEASE SEE THE PRINTED NAME AND LICENSE
 # FOR ENGINEER IS REQUIRED FOR ALL
 SHEETS AND FOR ALL TRADES WHEATHER OR
 NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 2)NOTE: PLEASE SEE "NEW " PANEL A/C-2
 DOES NOT SHOW CLEARENCE REQUIRED UNDER
 110.26.
  
 3)NOTE: PLEASE CORRELATE ELECTRICAL
 RISER WITH MDP SCHEDULE FOR GROUNDING
 CONDUCTOR.ONE SHOWS #2, THE OTHER #3.
  
 4)NOTE: PLEASE CLARIFY SIZE OF EXISTING
 A/C PANEL.
 PLEASE SEE RISER SHOWS MDP AS 225A AND
 MDP PANEL SCHEDULE AS 400A?
  
 5)NOTE: PLEASE CORRELATE "EXISTING
 HOUSE' PANEL.?? PLEASE SEE RISER SHOWS
 THIS PANEL BEING FED FROM MDP, HOWEVER,
 MDP PANEL SCHEDULE DOES NOT INDICATE ANY
 FEED FOR THIS PANEL?
 PLEASE SEE "EXISTING HOUSE" PANEL
 SCHEDULE, PANEL DETAILS MENTIONS, "FED
 FROM FIRST FLR PANEL"??
 215.5
  
 6)NOTE: PLEASE SHOW LOAD CALCULATION FOR
 NEW A/C-2 PANEL, INCLUDING LARGEST MOTOR
 LOAD AT 125%.
 PLEASE SUBMIT LOAD CALCULATION FOR MDP,
 SHOWING.
 215.5,220
  
 PLEASE SEE ONE SET HAS SOME OF THE ABOVE
 ITEMS REDLINED AT AREAS OF NOTES.
  
 PLEASE SEE ANY POSSIBEL COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  