| 2005-03-22 00:00:00 | ***** UNSAT ***** |
| | |
| | |
| | PLEASE SEE PLANS ARE ONLY IN FOR "PLAN |
| | REVIEW" AT THIS TIME AND NOT FOR PERMIT. |
| | |
| | 1)NOTE: PLEASE SEE MISSING INFORMATION |
| | ON TITLE BLOCK AS REQUIRED UNDER FAC |
| | 61G15-23.002. |
| | PLEASE SEE THE PRINTED NAME AND LICENSE |
| | # FOR ENGINEER IS REQUIRED FOR ALL |
| | SHEETS AND FOR ALL TRADES WHEATHER OR |
| | NOT COMMENT IS MADE BY OTHER |
| | REVIEWER(S). |
| | |
| | 2)NOTE: PLEASE SEE "NEW " PANEL A/C-2 |
| | DOES NOT SHOW CLEARENCE REQUIRED UNDER |
| | 110.26. |
| | |
| | 3)NOTE: PLEASE CORRELATE ELECTRICAL |
| | RISER WITH MDP SCHEDULE FOR GROUNDING |
| | CONDUCTOR.ONE SHOWS #2, THE OTHER #3. |
| | |
| | 4)NOTE: PLEASE CLARIFY SIZE OF EXISTING |
| | A/C PANEL. |
| | PLEASE SEE RISER SHOWS MDP AS 225A AND |
| | MDP PANEL SCHEDULE AS 400A? |
| | |
| | 5)NOTE: PLEASE CORRELATE "EXISTING |
| | HOUSE' PANEL.?? PLEASE SEE RISER SHOWS |
| | THIS PANEL BEING FED FROM MDP, HOWEVER, |
| | MDP PANEL SCHEDULE DOES NOT INDICATE ANY |
| | FEED FOR THIS PANEL? |
| | PLEASE SEE "EXISTING HOUSE" PANEL |
| | SCHEDULE, PANEL DETAILS MENTIONS, "FED |
| | FROM FIRST FLR PANEL"?? |
| | 215.5 |
| | |
| | 6)NOTE: PLEASE SHOW LOAD CALCULATION FOR |
| | NEW A/C-2 PANEL, INCLUDING LARGEST MOTOR |
| | LOAD AT 125%. |
| | PLEASE SUBMIT LOAD CALCULATION FOR MDP, |
| | SHOWING. |
| | 215.5,220 |
| | |
| | PLEASE SEE ONE SET HAS SOME OF THE ABOVE |
| | ITEMS REDLINED AT AREAS OF NOTES. |
| | |
| | PLEASE SEE ANY POSSIBEL COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |