| Date |
Text |
| 2005-04-11 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05030625 |
| | ADD: 2240 PALM BEACH LAKES |
| | CONT:PLAN REVIEW/ ROBERT SHORR |
| | TEL: (561)301-4011 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | A) PROVIDE THE MINIMUM BUILDING TYPE? |
| | B) PROVIDE FLOOR PLAN INDICATING TENANT |
| | SEPERATION,704.3. 1ST & 2ND FLOOR |
| | INDICATE TENANT SEPERATION BUT 3RD AND |
| | 4TH FLOOR DO NOT. |
| | C) GENERAL NOTE# 4," REPLACE DOORS IN |
| | COORIDOR WITH 20 MINUTE FIRE RATED |
| | ASSEMBLIES AS NECESSARY", PROVIDE A DOOR |
| | SCHEDULE OR OTHER MEANS TO IDENTIFY |
| | WHICH DOOR ASSEMBLIES WILL BE REPLACED |
| | UNDER THIS PERMIT. |
| | D) WHERE RATED WALLS ARE TO HAVE "FIRE |
| | WALL RESTORATION" PROVIDE THE UL LISTING |
| | OR GYPSUM LISTING NUMBERAND RATING IN |
| | HRS.704.2.1.2. |
| | E) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| | STOP PARTITIONS, HORIZONTAL EXIT PART- |
| | ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| | TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | F) 705.7.1 JOINTS INSTALLED IN OR BE- |
| | TWEEN FIRE RESISTANT WALLS, FIRE RESIS- |
| | TANT FLOORS OR FLOOR/ CEILING ASSEMBLIES |
| | AND FIRE RESISTANT ROOFS OR ROOF/ CEIL- |
| | ING ASSEMBLIES SHALL BE PROTECTED BY AN |
| | APPROVED FIRE RESISTANT JOINT SYSTEM |
| | DESIGNED TO RESIST THE PASSAGE OF FIRE |
| | FOR A PERIOD NOT LESS THAN THE RE- |
| | QUIRED FIRE RESISTANCE RATING OF THE |
| | WALL, FLOOR OR FLOOR IN OR BETWEEN |
| | WHICH IT IS INSTALLED. |
| | |
| | 2) SEE M-2 STAIRWELL SHAFT CONSTRUCTION, |
| | SEE 705.2.3.5 OPENINGS IN SHAFT |
| | ENCLOSURES SHALL BE PERMITTED WHEN |
| | LIMITED TO THOSE NESSECARY FOR THE |
| | PURPOSES OF THE SHAFT. PERMITTED |
| | OPENINGS IN SHAFT ENCLOSURES SHALL BE |
| | PROTECTED WITH OPENING PROTECTIVES |
| | HAVING A FIRE RESISTANCE IN ACCORDANCE |
| | WITH TABLE 705.1.2. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |