| 2005-03-10 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | F.S.= FLORIDA (STATE) STATUTE |
| | |
| | 1) FBC 1606.2.5THE SUBMITTED FLAT ROOF |
| | PRODUCT APPROVAL NOA ONLY LISTS SYSTEMS |
| | WITH MAXIMUM DESIGN PRESSURE OF LESS |
| | THAN -89 PSF.ALSO, EACH SYSTEM CITES |
| | GENERAL LIMITATION #9 (SEE PAGES 6 |
| | THROUGH 12 OF 13).GENERAL LIMITATION |
| | #9 PROHIBITS RATIONAL ANALYSIS OR |
| | EXTRAPOLATION TO ENHANCE THE ALLOWABLE |
| | UPLIFT PRESSURE AT PERIMETER AND CORNER |
| | AREAS BY REDUCING THE FASTENER SPACING |
| | IN THESE AREAS.SELECT AN ALTERNATIVE |
| | PRODUCT APPROVAL THAT DOES NOT CITE |
| | GENERAL LIMITATION #9.ALTERNATIVELY IF |
| | THE SELECTED PRODUCT APPROVAL DOES CITE |
| | GENERAL LIMITATION #9, IT MUST HAVE A |
| | MAXIMUM DESIGN PRESSURE THAT EXCEEDS THE |
| | PRESSURE IN ROOF ZONE 3 (TYPICALLY -89 |
| | PSF FOR MEAN ROOF HEIGHT OF 30 FEET OR |
| | LESS). |
| | |
| | 2) THE FLAT ROOF PRODUCT APPROVAL SHEETS |
| | MUST BE MARKED, AS APPROPRIATE, TO |
| | IDENTIFY WHICH SYSTEM IS TO BE USED SO |
| | THAT THE MAXIMUM DESIGN PRESSURE CAN BE |
| | VERIFIED |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | TELEPHONE: (561) 805 6716ROBERT BROWN |