| 2005-06-03 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA STATUTES |
| | |
| | FROM PREVIOUS REVIEW: |
| | 2. SHT A2 PROCESSING UNIT MAY REQUIRED A |
| | NEUTRALIZING TANK. CONTACT RODNEY COMPO, |
| | ENVIRONMENTAL COMPLIANCE (561) 837-4074, |
| | OR E-MAIL [email protected]. SUBMIT HIS |
| | DETERMINATION WORKSHEET WITH PLANS WHEN |
| | RESUBMITTING PLANS FOR REVIEW. |
| | 5. SHT P1 WATER RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN, NOR DOES IT MEET |
| | THE CODE REQUIREMENTS. SECTION 104.2.1. |
| | B. SHOW REQUIRED WATER HAMMER ARRESTORS |
| | INSTALLED PER PDI-WH 201 & MANUF. |
| | INSTALLATION INSTRUCTIONS. |
| | F. AIR CHAMBERS ARE NOT APPROVED. |
| | SECTION 604.9. - DELETE FROM RISER. |
| | 6. SHT P2 THE FOLLOWING INFORMATION FOR |
| | THE ACCESSIBLE TOILET ROOM SHALL BE |
| | SHOWN ON THE DETAIL SHT P2 AND THE FLOOR |
| | PLAN: |
| | A. CLEAR FLOOR SPACE 11-4.16.2 - W/C |
| | B. CLEAR FLOOR SPACE 11-4.19.3 - LAV |
| | 7. ALL DEVICES INTENDED TO SERVE SOME |
| | SPECIAL FUNCTION SUCH AS PROCESSING, AND |
| | THAT CONNECT TO THE WATER SUPPLY SYSTEM, |
| | SHALL BE PROVIDED WITH PROTECTION |
| | AGAINST BACKFLOW. SECTION 608.3 - PLEASE |
| | PROVIDE METHOD OF PROTECTION. SECTION |
| | 104.2.1. - RESPONSE NOTED, BUT PER |
| | SECTION 608.15.1 OPENINGS AND OUTLETS |
| | EQUIPPED FOR HOSE CONNECTION SHALL BE |
| | PROTECTED BY MEANS OTHER THAN AN AIR |
| | GAP. |
| | ****************NEW COMMENTS************ |
| | 1B. SHT P1 SANT. RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN, NOR DOES IT MEET |
| | CODE REQUIREMENT. |
| | A. ONLY SHOW FIXTURES THAT WILL BE ON |
| | THE RISER DIAGRAM. |
| | B. THE SINK AND PROCESSOR SHALL NOT |
| | DRAIN THROUGH THE HORIZONTAL WET VENT |
| | FOR THE BATHROOM FIXTURES. SECTION 909.1 |
| | SEE RED LINE CORRECTIONS FOR THIS ON THE |
| | RISER DIAGRAM AND THE FLOOR PLAN. |
| | C. FIXTURE IS MISLABELED. NEW SINK IN |
| | DARK ROOM LABELED AS EXISTING LAV. |
| | D. WASH MACHINE IS NOT VENTED AND A |
| | CLEANOUT 4' ABOVE THE FLOOR IS REQUIRED |
| | AT WASH MACHINE. |
| | 2B. SHT P1 WATER RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN, NOR DOES IT MEET |
| | CODE REQUIREMENTS. |
| | A. INDICATE WHERE THE HOT AND COLD |
| | WATER LINES PAST THE LAST FIXTURES TO |
| | THE LEFT AND RIGHT ARE CONNECTING TO? |
| | SECTION 104.2.1. |
| | B. THE WATER CLOSET IS NOT SHOWN ON THE |
| | RISER DIAGRAM. |
| | C. NEW SINK IN DARK ROOM LABELED AS |
| | EXISTING LAV. |
| | D. DELETE ALL AIR CHAMBERS, AND SHOW |
| | WATER HAMMER ARRESTORS AT WASH MACHINE |
| | AS REQUIRED IN SECTION 604.9. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |