| 2005-03-23 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | |
| | |
| | 1) SHT A2 ALTERED PORTIONS OF EXISTING |
| | BUILDINGS AND FACILITIES REQUIRED TO BE |
| | ACCESSIBLE BY 11-4.1.6 SHALL COMPLY WITH |
| | 11-4.1 THROUGH 11-4.35. SECTION |
| | 11-4.1.1(1)(A).- IF EXISTING ELEMENTS |
| | , SPACES, OR COMMON AREAS ARE ALTERED, |
| | THEN EACH SUCH ALTERED ELEMENT, SPACE, |
| | FEATURE, OR AREA SHALL COMPLY WITH THE |
| | APPLICABLE PROVISIONS OF 11-4.1.1 TO |
| | 11-4.1.3 MINIMUM REQUIREMENTS FOR NEW |
| | CONSTRUCTION. - THE "NEW DARKROOM" HAS A |
| | WATER CLOSET AND "LAV" IN IT AND IS |
| | STILL CONSIDERED A TOILET ROOM AND SHALL |
| | BE ACCESSIBLE. |
| | 2) SHT A2 PROCESSING UNIT MAY REQUIRE A |
| | NEUTRALIZING TANK. CONTACT RODNEY COMPO, |
| | ENVIRONMENTAL COMPLIANCE (561) 837-4074 |
| | OR E-MAIL [email protected]. SUBMIT HIS |
| | DETERMINATION WORKSHEET WITH PLANS WHEN |
| | RESUBMITTING PLANS FOR REVIEW. |
| | 3) A DRINKING FOUNTAIN IS REQUIRED PER |
| | TABLE 403.1. |
| | 4) SHT P1 SANITARY RISER DIAGRAM DOES |
| | NOT REFLECT THE FLOOR PLAN, NOR DOES IT |
| | MEET CODE REQUIREMENTS: SEC 104.2.1. |
| | A) THE WASH MACHINE IS NOT SHOWN ON THE |
| | SANT. RISER. |
| | B) SHOW ALL PIPE SIZES |
| | C) FLOOR PLANS INDICATES A P-TRAP AND |
| | STANDPIPE FOR THE PROCESSOR THATS NOT |
| | SHOWN ON THE RISER DIAGRAM. |
| | 5) SHT P1 WATER RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN, NOR DOES IT MEET |
| | THE CODE REQUIREMENTS: SECTION 104.2.1. |
| | A) SHOW ALL PIPE SIZES |
| | B) SHOW REQUIRED WATER HAMMER ARRESTORS |
| | INSTALLED PER PDI-WH 201 & MANUF. |
| | INSTALLATION INSTRUCTIONS NEAR THE |
| | FIXTURE IN AN "EFFECTIVE RANGE" NOT IN |
| | THE CEILING. |
| | C) FULL OPEN VALVES ARE REQUIRED ON ALL |
| | WATER DOWN-FEED PIPES. 606.1(4) |
| | D) IDENTIFY ALL FIXTURES ON THE RISER, |
| | AND SHOW THE WASH MACHINE AND ALL |
| | EXISTING FIXTURES. |
| | E) SHOW ALL REQUIRED VALVES |
| | F) AIR CHAMBERS ARE NOT APPROVED. |
| | SECTION 604.9 |
| | 6) SHT P2 THE FOLLOWING INFORMATION FOR |
| | THE ACCESSIBLE TOILET ROOM SHALL BE |
| | SHOWN ON THE DETAIL SHT P2 AND THE FLOOR |
| | PLAN: |
| | A) CLEAR FLOOR SPACE 11-4.16.2 - W/C |
| | B) CLEAR FLOOR SPACE 11-4.19.3 - LAV |
| | C) EXPOSED PIPES & SURFACES 11-4.19.6 |
| | D) A 5' TURNING AREA REQUIRED IN EACH |
| | TOILET ROOM. 11-4.22.3 |
| | 7) ALL DEVICES INTENDED TO SERVE SOME |
| | SPECIAL FUNCTION SUCH AS PROCESSING, AND |
| | THAT CONNECT TO THE WATER SUPPLY SYSTEM, |
| | SHALL BE PROVIDED WITH PROTECTION |
| | AGAINST BACKFLOW. SECTION 608.3. - |
| | PLEASE PROVIDE METHOD OF PROTECTION. |
| | SECTION 104.2.1. |
| | 8) PROVIDE DETAIL FOR KITCHEN SINK |
| | ACCESSIBLITY. SHOW THE FOLLOWING |
| | INFORMATION: |
| | A) HEIGHT 11-4.24.2 |
| | B) KNEE CLEARANCE 11-4.24.3 |
| | C) SINK DEPTH 11-4.24.4 |
| | D) CLEAR FLOOR SPACE 11-4.24.5 SHALL BE |
| | PROVIDED TO ALLOW FORWARD APPROACH, AND |
| | SHALL EXTEND A MAXIMUM 19" UNDERNEATH |
| | THE SINK. |
| | E) EXPOSED PIPES & SURFACES 11-4.24.6 |
| | F) FAUCETS 11-4.24.7 |
| | G) SHOW TURNING AREA IN KITCHEN. |
| | |
| | REVIEW BY KEN STEVENS |