| 2005-03-14 00:00:00 | ************ UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SEE SERVICE NOTE MENTIONS |
| | |
| | UPGRADE EXISTING ELECTRICAL RISER. |
| | PLEASE VERIFY WHAT APPAEARS TO BE A |
| | "TAP" FROM 200A MAIN DISC WHICH ALREADY |
| | FEEDS AND EXISTING 200A MLO PANEL. |
| | 240.21 |
| | |
| | 2)NOTE: PLEASE SUBMIT LOAD CALCUALTIONS |
| | FOR EXISTING 200A DISCONNECT AND FOR |
| | EXSITNG 1200A MAIN SERVICE. |
| | 220.3,220.10,220.11,220.13 ETC. |
| | PLEASE SEE ALL CONTINOUS LOADS TO BE |
| | SHOWN AT 125%.215.3,230.42 ETC |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE SEE CONDUCTOR SIZE SHOWN |
| | FROM 150A DISCONNETC. #1? |
| | PLEASE SEE 310.16 75DEGREE COLUMN FOR |
| | MIN AWG FOR 150A'S. |
| | |
| | 4)NOTE: PLEASE INCLUDE ALL CIRCUITNG ON |
| | PLANS FOR NEW AND CORRELATE WITH A PANEL |
| | SCHEDULE TO BE SUBMITTED. |
| | PLEASE ALSO SEE 700.12E FOR CIRCUITING |
| | OF ANY EM/EXT LTS WHICH MAY OR MAY NOT |
| | BE REQUIRED. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | PLEASE SUBMIT ONE COPY OF OLD SHEETS FOR |
| | REFERENCE ONLY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |