| Plan Review Notes For Permit 05030502 |
| Permit Number |
05030502 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-06-08 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1- TRUSS ANCHOR SCHEDULE: CONNECTOR F IN | | | ENGINEER'S LETTER SAYS THAT CONNECTOR IS | | | (2)B+USP HD2X-2X WHILE ANCHOR SCHEDULE | | | SHOWS (2)B + USP HDPT. THESE ARE 2 | | | DIFFERENT CONNECTORS. REVISE AS REQ'D. | | | | | | 2- PROVIDE FLORIDA OR APPLY FOR LOCAL | | | PRODUCT APPROVAL FOR BAHAMA SHUTTERS | | | SHOWING INSTALLATION FOR 140MPH WIND | | | LOAD ZONE. | | | | | | 3- SPECIFY FIREBLOCKING MATERIAL AND | | | LOCATION IN STAIR SECTION AS REQUIRED BY | | | SEC. 2305.1.4 FBC 2001. |
|