2005-05-24 00:00:00BUILDING REVIEW CHECKLIST:
  
 1- ENTRY DOOR TO HAVE LEAF THAT ALLOWS
 32" MIN. CLEAR OPENING AS REQ'D BY TABLE
 1004 FBC 2001. 32" WIDE DOOR DOESN'T
 PROVIDE THE 32" CLEAR OPENING. REVISE
 DOOR SCHEDULE AS REQUIRED.
  
 2- UPDATE TRUSS ANCHOR SCHEDULE. SEE
 2005 SIMPSON OR USP CATALOGUE THAT WERE
 REVISED TYPE AND NUMBER OF FASTENERS TO
 COMPLY WITH SEC. 1609.4.3 FBC 2001.
 IF TRUSS ANCHOR SCHEDULE AND CONNECTORS
 SPECIFIED ON PLANS SHOW DIFFERENT TYPE
 AND NAILING NUMBER OTHER THAN THOSE
 TESTED & PUBLISHED BY THE MANUFACTURER,
 THEN, COMPLETE ENGINEERING ANALYSIS IS
 REQUIRED TO DEMONSTRATE COMPLIANCE WITH
 SEC. 1609.4.3 FBC 2001.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC
 2001. (NOTE: REVISE TRUSS ANCHOR
 SCHEDULEIN SHEET S3 AND SD1).
  
 3- ENERGY CALCULATIONS: UNDER ATTIC AREA
 WAS NOT REVISED AS REQUESTED ON PREVIOUS
 CHECKLIST. SEE SEC. 602.1.ABC.1.2
 CHAPTER 13 FBC 2001 AND REVISE AS REQ'D.
  
 4- ARCHITECTURAL PLANS SHOW LICENSE
 #33849. WHAT'S THIS LICENSE FOR?. UNABLE
 TO MATCH THIS LICENSE # WITH THE FLORIDA
 WEBSITE.
  
 5- SPECIFY IN PLANS HOW OPERABLE
 SHUTTERS WILL COMPLY WITHSEC. 1005.4.4
 FBC 2001. HOW ARE MIN. CLEAR OPENINGS
 MAINTAINED.
  
 6- POSTS SHOWN ON BALCONY GUARDRAIL
 DON'T MATCH STRUCTURAL PLANS. REVISE AS
 REQUIRED.
  
 7- ELEVATIONS ON SHEET A-4 ARE NAMED
 INCORRECTLY. SEE SURVEY FOR PROPER
 ORIENTATION AND REVISE AS REQUIRED.
  
 8- SPECIFY FIREBLOCKING IN ALL AREAS AS
 REQUIRED BY SEC. 2305.1 FBC 2001. SHOW
 FIREBLOCKING IN ALL BLDG SECTIONS,
 STAIRS ETC.
  
 9- SPECIFY DRAFSTOPPING LOCATION AND
 MATERIAL IN 2ND FLOOR FRAMING PLAN AS
 REQUIRED BY SEC. 2305.2.2 FBC 2001.
 (NOTE: THIS DRAFSTOPPPING HAS NOTHING TO
 DO WITH THE FIREPLACE).
  
 10- 2ND FLOOR FRAMING PLAN IS MISSING
 INFORMATION. SPECIFY ALL CONNECTORS
 AROUND STAIRWELL OPENING FRAMING
 MEMBERS. SEC. 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.
  
 11- DETAIL 13/SD2 DON'T MATCH 2ND FLOOR
 FRAMING PLAN. REVISE AS REQUIRED. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 12- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL ONLY FOR DOORS AND WINDOWS TO
 BE USED. TO EXPEDITE REVIEW PROCESS AND
 AVOID CONFUSION CLEARLY IDENTIFY WHICH
 DOOR/WINDOW PRODUCT APPROVAL WILL BE
 USED. DON'T SUBMIT PRODUCT APPROVALS
 THAT WILL NOT BE USED.
 ***SAME THING APPLIES TO MULLIONS THERE
 ARE SEVERAL PRODUCT APPROVALS SUBMITTED.
  
 13- OWES $280.76 FOR UPDATED VALUATION
 AND RADON FEES.
  
 14- SHEET SD1: UPDATE ALL GENERAL NOTES.
 SEE COMMENTS ON PLANS. SEE CHAPTER 19
 AND 35 FOR PROPER REFERENCES AND
 EDITIONS TO BE USED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.