| Plan Review Notes For Permit 05030502 |
| Permit Number |
05030502 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-03-26 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1) ALL ARCHITECTURAL SHEET AND PM&E | | | PLANS, SECTION 104.2.1. ALL INFORMATION, | | | DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME | | | AND SIGNATURE OF THE PERSON RESPONSIBLE | | | FOR THE DESIGN. | | | 2) SHTS S1, S2, S3, SD1 & SD2 REQUIRE A | | | CERTIFICATE OF AUTHORIZATION NUMBER IN | | | THE TITLE BLOCK PER 61G15-23-002(2) AND | | | FS 471.025. - ALSO THE DATE THAT THE | | | SIGNATURE AND SEAL ARE AFFIXED TO THE | | | PLANS SHALL BE ENTERED ON THE SEAL PER | | | FAC 61G15-23.002(1) & FS 471.025. | | | 3) SHT P2 SANITARY RISER DIAGRAM DOES | | | NOT MEET CODE RQUIREMENTS. | | | A) THE W/M IS NOT VENTED SEC 901.2.1. | | | B) W/M CLEANOUT SHALL BE LOCATED 4' AFF | | | FOR ACCESS. SECTION 708.10 | | | C) BIDET AND SHOWER ARE NOT VENTED IN | | | THE MASTER BATH. SECTION 901.2.1. | | | D) TUB NOT IDENTIFIED IN MASTER | | | BATHROOM. SECTION 104.2.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|