| Notes |
| Date |
Text |
| 2005-03-31 00:00:00 | PLAN DENIED | | | 1) REFER TO SECTION 307.2.3 AUXILIARY | | | DRAIN PANS.DRAIN PANI MUST HAVE A DEPTH | | | OF 1 1/2 IN. | | | 2) NO SIZE ON RETURN AIR GRILL IN MASTER | | | BEDROOM. | | | 3) NEED EXHAUST FAN IN IN MASTER BATH | | | ROOM # 213. | | | 4) NEED SIZE OF DUCT FOR RETURN AIR IN | | | BEDROOM #3. | | | 5) REFER TO SECTION 306.3. NEED 30IN | | | CLEARANCE FOR SERVICE. | | | 6)SERVICE PLNALS FOR AIRHANDLERS MUST BE | | | NO MORE THAN 6 FT. FROM ATTIC | | | ACCESS.SECTION 610.1. ABC.3.5.2 FLORIDA | | | ENERGY CODE. | | | PLAN REVIEW BY HAROLD MOSER | | | (561)805-6732 |
|