2005-03-31 00:00:00PLAN DENIED
 1) REFER TO SECTION 307.2.3 AUXILIARY
 DRAIN PANS.DRAIN PANI MUST HAVE A DEPTH
 OF 1 1/2 IN.
 2) NO SIZE ON RETURN AIR GRILL IN MASTER
 BEDROOM.
 3) NEED EXHAUST FAN IN IN MASTER BATH
 ROOM # 213.
 4) NEED SIZE OF DUCT FOR RETURN AIR IN
 BEDROOM #3.
 5) REFER TO SECTION 306.3. NEED 30IN
 CLEARANCE FOR SERVICE.
 6)SERVICE PLNALS FOR AIRHANDLERS MUST BE
 NO MORE THAN 6 FT. FROM ATTIC
 ACCESS.SECTION 610.1. ABC.3.5.2 FLORIDA
 ENERGY CODE.
 PLAN REVIEW BY HAROLD MOSER