| Plan Review Notes For Permit 05030502 |
| Permit Number |
05030502 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-03-17 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | | | | 1} PER 210.11.C.3 THERE MUST BE A | | | MINIMUM OF TWO SMALL APPLIANCE CIRCUITS | | | IN THE KITCHEN. | | | | | | 2} PLEASE NOTE THAT THE 20 AMP CIRCUIT | | | FEEDING THE BATHROOM(S) SHALL HAVE NO | | | OTHER OUTLETS. ALL THOSE CIRCUITS FEED | | | SOMETHING OUTSIDE THE BATHS ON THE | | | SECOND FLOOR. SEE REVIEWED SET OF PLANS. | | | SEE 210.11(C)(3). | | | | | | 3} THE LIVING ROOM IS MISMARKED ON SHEET | | | E1. | | | | | | 4} NOTE REQUIREMENTS FOR KITCHEN | | | COUNTERTOP RECEPTACLE SPACING PER | | | 210.52(C), ALSO GFI'S PER 210.8.A.6. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | |
|