| 2005-04-01 00:00:00 | CHECKLIST: |
| | 1-PAY IMPACT FEES TO PALM BEACH COUNTY. |
| | BRING BACK STAMPED DRAWINGS AND PAID |
| | RECEIPT. |
| | |
| | 2- NEED RECORDED NOTICE OF COMMENCEMENT. |
| | |
| | 3- ENTRY DOOR TO HAVE LEAF THAT ALLOWS |
| | 32" MIN. CLEAR OPENING AS REQUIRED BY |
| | TABLE 1004 FBC 2001. 30"WIDE DOOR |
| | DOESN'T PROVIDE 32" MIN. CLEAR OPENING. |
| | |
| | 4- SPECIFY ROOF TILE FASTENING AS |
| | REQUIRED BY SEC. 104.2.1.1 OF CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 5- UPDATE TRUSS ANCHOR SCHEDULE. SEE |
| | LATEST CATALOGUE FOR TYPE AND NUMBER OF |
| | FASTENERS SPECIFIED. PROVIDE COMPLETE |
| | ENGINEERING CALCULATIONS THAT COMPLY |
| | WITH SEC. 1609.4.3 FBC 2001 FOR TYPE AND |
| | NUMBER OF FASTENERS THAT DIFFER FROM |
| | THOSE TESTED AND PUBLISHED BY |
| | MANUFACTURER TO COMPLY WITH ABOVE |
| | BUILDING CODE SECTION. |
| | |
| | 6- PROVIDE SOIL TEST REPORT. |
| | |
| | 7- ENERGY CALCULATIONS: A) REVISE UNDER |
| | ATTIC AREA. SEE SEC. 602.1.ABC.1.2 |
| | CHAPTER 13 FBC 2001. |
| | B) PROVIDE COMPLETE INFORMATION ON TOP |
| | OF FORM. NEED OWNER & BUILDER INFO. |
| | |
| | 7- SPECIFY CEILING FAN SIZES ON PLANS |
| | AS REQUIRED BY TABLE 6-6 CHAPTER 13 FBC |
| | 2001 WHEN CEILING FAN CREDIT IS TAKEN |
| | IN THE ENERGY CALCULATIONS. |
| | |
| | 8- ARCHITECTURAL PLANS NEED TO HAVE NAME |
| | AND SIGNATURE OF PERSON RESPONSIBLE FOR |
| | THE DESIGN. SEC. 104.2.1 CITY AMENDMENTS |
| | TO FBC 2001. |
| | |
| | 9- ENGINEER TO DATE PLANS WHEN SIGNING |
| | AND SEALING DOCUMENTS AS REQUIRED BY |
| | CHAPTER 471 FL. STATUTES. |
| | |
| | 10- SPECIFY WHAT ARE DOORS DO1 AND DO2. |
| | THEY ARE NOT INCLUDED IN THE DOOR |
| | SCHEDULE. SPECIFY SIZE, MATERIAL, ETC. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | |
| | 11- PROVIDE COMPLETE SPECS FOR FURRING |
| | OF WALL AT LOGGIA AND BALCONY ABOVE. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | |
| | 12- PRIVACY/FENCE WALL REQUIRES SEPARATE |
| | PERMIT AND EASEMENT RELEASE FROM |
| | UTILITIES. |
| | |
| | 13- REVISE STAIRS RATIO TO COMPLY WITH |
| | SEC. 1007.3.1 EXCEPTION #1 FBC 2001. |
| | |
| | 14- EGRESS WINDOWS ON BEDROOMS 1 AND 2 |
| | NEED PROVIDE 5.7S.F. MIN. NET CLEAR |
| | OPENING TO COMPLY WITH SEC. 1005.4.4 FBC |
| | 2001. PROVIDE MANUFATURER CUT SHEETS |
| | THAT SHOW NET CLEAR OPENING OF WINDOW |
| | SPECIFIED ON PLANS. |
| | |
| | 15- EXTERIOR WEST ELEVATION SHOWS |
| | DECORATIVE SHUTTERS ATTACHED TO WINDOWS |
| | ON BEDROOM #1. THESE SHUTTERS ARE |
| | BLOCKING THE EGRESS REQ'D BY SEC. |
| | 1005.4.4 FBC. REVISE AS REQUIRED. |
| | |
| | 16- ATTIC ACCESS TO BE 20"X36" MIN. |
| | REVISE SIZE OF ATTIC ACCESS SHOWN ON THE |
| | SECOND FLOOR ROOF. SEC. 2309.6 FBC 2001. |
| | |
| | 17- PROVIDE COMPLETE DETAILS & SPECS |
| | FOR BALCONY GUARDRAIL. SEE SEC. 1015 FBC |
| | 2001 FOR REQUIREMENTS. |
| | |
| | 18- SHEET A-3. CLARIFY HOW ARE GARAGE |
| | DOORS GOING TO BE OPEN IF THEY ARE |
| | OBSTRUCTED BY DECORATIVE SHUTTERS. |
| | |
| | 19- POSTS SHOWN ON BALCONY GUARDRAIL |
| | SHOWN ON PLANS DON'T MATCH LOCATION AND |
| | NUMBER OF POSTS SHOWN ON EXTERIOR |
| | ELEVATION. REVISE AS REQUIRED. |
| | |
| | 20- PROVIDE MANUFATURER'S SPECS THAT |
| | ALLOW CHIMNEY CAP AS SHOWN ON |
| | ELEVATIONS. AND, IF ALLOWED BY |
| | MANUFACTURER, THEN, PROVIDE COMPLETE |
| | SPECS AND CLEARANCES AS REQUIRED. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | |
| | 21- CEARLY PROVIDE FASTENING SPECS FOR |
| | ROOF SHEATHING. SEE TABLE 2306.1 OF CITY |
| | AMENDMENTS TO FBC 2001 FOR REQUIRED TYPE |
| | AND SPACING OF NAILS FOR MEAN ROOF |
| | HEIGHT OVER 25'-0". |
| | ALSO, MAKE SURE THAT SPECS ON ALL |
| | RELATED DETAILS MATCH SPECS SHOWN ON |
| | SHEET S3. |
| | |
| | 22- CHIMNEY HEIGHT TO COMPLY WITH SEC. |
| | 2804.2.4. 2'-0" ABOVE 10'-0" HORIZONTAL |
| | DIRECTION (SEE ATTACHED SAMPLE). |
| | NOTE: KEEP IN MIND ZONING HEIGHT |
| | RESTRICTIONS TOO. |
| | |
| | 23- SPECIFY FIREBLOCKING IN ALL AREAS AS |
| | REQUIRED BY SEC.2305.1 FBC 2001. |
| | |
| | 24- SPECIFY DRAFSTOPPING LOCATION AND |
| | MATERIAL IN SECOND FLOOR FRAMING PLAN AS |
| | REQ'D BY SEC. 2305.2.2 FBC 2001. |
| | |
| | 25- SECOND FLOOR FRAMING PLAN IS MISSING |
| | FRAMING AROUND OPENING FOR STAIRS. |
| | |
| | 26- DETAIL 13/SD2 DON'T MATCH CONDITIONS |
| | SHOWN ON 2ND FLOOR FRAMING PLAN. REVISE |
| | AS REQUIRED. SEE TOP OF DETAIL AND |
| | SPECIFY ALL FASTENERS. SEC. 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | |
| | 27- PROVIDE DETAIL/SECTION SHOWING HOW |
| | IS STRUCTURAL DOOR BUCK DETAIL ATTACHED |
| | TO STEEL COLUMN @ FAMILY ROOM. SPECIFY |
| | SIZE OF BUCK, FASTENER TYPE AND SPACING. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | |
| | 28- PROVIDE COMPLETE SECTION DETAILS FOR |
| | CANTILEVERED BALCONIES. CLARIFY HOW IS |
| | THE 48" HOOK INSTALLED. SPACING , ETC. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | |
| | 29- HOUSE IS IN FLOOD ZONE A5. PROVIDE |
| | CURRENT SURVEY SHOWING NEW HOUSE LAYOUT |
| | AND FINISH FLOOR ELEVATIONS. |
| | |
| | 30- PRODUCT APPROVALS: A)PROVIDE ONLY |
| | PRODUCT APPROVAL FOR TYPE OF DOORS AND |
| | WINDOWS TO BE INSTALLED IN THIS HOUSE. |
| | B) PROVIDE PRODUCT APPROVAL FROM ONE |
| | COMPANY ONLY. DECIDE IF USING PGT |
| | WINDOWS OR CONSTRUCTION GLASS |
| | INDUSTRIES. |
| | NOTE: PLANS CALL FOR PGT WINDOWS/DOORS. |
| | C) SPECIFY SIZE OF GARAGE DOORS. DOOR |
| | SCHEDULE DON'T SHOW ANY D13 & D14 DOORS. |
| | NOTE; PROVIDE GARAGE DOOR PRODUCT |
| | APPROVAL THAT MEET DESIGN PRESSURES |
| | CALCULATED BY THE ENGINEER OF RECORD. |
| | D) MAKE SURE THAT DADE COUNTY NOA |
| | REPORTS SUBMITTED MATCH NOA REPORTS THAT |
| | WERE SUBMITTED FOR FLORIDA PRODUCT |
| | APPROVAL AND MAKE SURE DRAWINGS ARE |
| | LEGIBLE. |
| | E) HANSON ROOF TILE APPLIED FOR FLORIDA |
| | PRODUCT APPROVAL WITH SBCCI REPORT. |
| | PROVIDE COPY OF SAME SBCCI REPORT |
| | SUBMITTED FOR FLORIDA PRODUCT APPROVAL. |
| | |
| | 31- OWES $280.76 FOR UPDATED VALUATION |
| | AND RADON FEES. |
| | |
| | 32- SHEET A-4: PROVIDE CORRECT NAME FOR |
| | ELEVATIONS. THEY ARE WEST AND NORTH |
| | ELEVATIONS. |
| | |
| | 33- SHEET A-7: SPECIFY HOW IS LOW WALL |
| | AT MEZZANINE ATTACHED TO THE FLOOR. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | |
| | 34- MAKE SURE SCALE NOTED ON DRAWINGS IS |
| | THE RIGHT SCALE. EG: REVISE SCALE ON |
| | SHEET A-7 AND A-8. |
| | |
| | 35- SHEET S1:A) FOOTING F4 IS NOT |
| | DRAWWN TO SCALE IN THE FOUNDATION PLAN. |
| | B) COLUMN SCHEDULE HAS INFORMATION |
| | WRITTEN BY HAND. ENGINEER NEED TO SIGN |
| | THAT CHANGE OR INCLUDE INFORMATION ON |
| | ORIGINAL CAD DRAWING. |
| | C) FOOTING SCHEDULE: FOOTING F1 DOESN'T |
| | MATCH DETAIL 4/SD1. CLARIFY NUMBER OF |
| | REBARS. 3 OR 4. REVISE AS REQUIRED. |
| | D) FOOTING TE1: CLARIFY IF USING ONE OR |
| | TWO REBARS. DWG SHOWS 1. NOTE SHOWS 2. |
| | REVISE AS REQUIRED. |
| | |
| | 36- SHEET SD1: UPDATE ALL GENERAL NOTES. |
| | SEE COMMENTS ON PLANS AND REFERENCE |
| | CURRENT STANDARD EDITIONS. SEE CHAPTERS |
| | 19 AND 35 OF FBC 2001. |
| | |
| | 37- SHEET SD2: SPECIFY SIZE OF NAILS TO |
| | FASTEN WINDOW/SGD BUCK. SEC. 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001 AND SECTION |
| | 1707.4.4.2 FBC 2001. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT (561)805-6712. |