Plan Review Notes For Permit 05030493
Permit Number 05030493
Review Stop P
Sequence Number 1
Notes
Date Text
2005-03-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHT A-1 CODE REFERENCED IS THE 1994
 STANDARD PLUMBING CODE. CODE ADOPTED IS
 THE FBC-2001. PLEASE INDICATE ON PLANS.
 SECTION 104.2.1.
 2) SHT A-3 DETAIL 8 SHOW CLEAR FLOOR
 SPACE FOR W/C 11-4.16.3, FLUSH CONTROLS
 11-4.16.5. FOR THE LAV SHOW FAUCETS
 11-4.19.5.
 3) SHT A-4 DETAIL 4 SHOW KNEE CLEARANCE
 11-4.24.3, SINK DEPTH 11-4.24.4, CLEAR
 FLOOR SPACE 11-4.24.5 WHICH SHALL BE
 PROVIDEDIN FRONT OF A SINK TO ALLOW
 FORWARD APPROACH WHICH SHALL EXTEND A
 MAXIMUM OF 19" UNDERNEATH THE SINK,
 EXPOSED PIPES & SURFACES 11-4.24.6,
 FAUCETS 11-4.24.7.
 4) SUBMIT A SANITARY RISER DIAGRAM
 SHOWING ALL PIPE SIZES, VENTS, & TRAPS.
 SECTION 104.3.1.1.
 5) SUBMIT A WATER RISER DIAGRAM SHOWING
 ALL PIPE SIZES, VALVES, WATER HAMMER
 ARRESTORS (IF REQUIRED BY 604.9) AND
 POINT OF CONNECTION. SECTION 104.3.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]