Notes
Date Text
2005-03-14 00:00:00******** UNSAT ********
  
 1)NOTE: PLEASE INCLUDE LOAD ON EXISTING
 GUTTER OR MAIN FOR 2ND FLR.RISER DOES
 NOT INDICATE ANY TYP OF DISC FROM
 BUS-DUCT RISER TO 2ND FLR ELECTRICAL RM
 GUTTER.
 PLEASE ALSO INCLUDE CONDUCTORS SIZES FOR
 GUTTER FEED.
 215.5
  
 2)NOTE: PLAN NOTE MENTIONS LOCATION OF
 TRANSFORMER TO BE ABOVE CEILING,PLEASE
 SHOW ON PLANS LOCATION OF TRNASFORMER.
 215.5/450.13,450.21 ETC.
 DIRECTLY ABOVE PANELS?
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  