| Plan Review Notes For Permit 05030481 |
| Permit Number |
05030481 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-03-24 00:00:00 | 1)PLEASE BE ADVISED THAT ALL MATERIAL | | | AND INSTALLATION SHALL MEET THE | | | REQUIREMENTS OF NFPA 24, 2002 EDITION. | | | | | | 2) FDC'S MUST REMAIN ACCESSIBLE AND | | | CLEAR OF OBSTRUCTIONS. PROTECTION MAY BE | | | REQUIRED IF MECHANICAL DAMAGE IS | | | ANTICIPATED. | | | | | | 3) BACKFLOW PREVENTORS AND PIV'S SHALL | | | HAVE ELECTRONIC SUPERVISION AND BE | | | SECURED WITH CHAINS AND LOCKS. | | | | | | | | | MIKE WENNERGREN, ACTING CAPTAIN | | | WPBFR(561) 835-2910 |
|