| Plan Review Notes For Permit 05030373 |
| Permit Number |
05030373 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-03-22 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT A-3 ACCESSIBLE SINKS. THE | | | FOLLOWING INFORMATION IS REQUIRED ON THE | | | SINK DETAILS: | | | A) SINK DEPTH 11-4.24.4 | | | B) CLEAR FLOOR SPACE 11-4.24.5 - SHALL | | | BE FORWARD APPROACH, MAXIMUM 19" | | | UNDERNEATH THE SINK. | | | C) PROVIDE CROSS SECTIONAL VIEW OF THE | | | PLAM. APRON TO SHOW COMPLIANCE WITH | | | FIGURE 31 CLEARANCES. | | | D) FAUCETS 11-4.24.7 | | | 2) SHT P0.1 WATER ISOMETRICS, THE WATER | | | HAMMER ARRESTORS SHALL BE LOCATED NEAR | | | THE FIXTURES IN AN "EFFECTIVE RANGE" NOT | | | IN THE CEILING AS SHOWN. (SEE PLUMBING | | | NOTE #13) | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|