Plan Review Notes
Plan Review Notes For Permit 05030373
Permit Number 05030373
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-03-30 00:00:001) THE CITY OF WEST PALM BEACH REQUIRES
 THE DUCT SMOKE DETECTORS TO BE WIRED
 INTO THE FIRE ALARM SYSTEM TO CAUSE A
 GENERAL FIRE ALARM UPON ACTIVATION. NOTE
 FA0.1 #17.
  
 2) FIRE EXTINGUISHERS SIZED 2A-10B-C ARE
 REQUIRED NOT TO EXCEED A TRAVEL DISTANCE
 OF 75 FEET.
  
  
 MIKE WENNERGREN, A/CAPTAIN WPBFR(561)
 835-2910