| Plan Review Notes For Permit 05030358 |
| Permit Number |
05030358 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-06-30 00:00:00 | ****** PLANS REDLINED ********** | | | | | | 1)NOTE: PLEASE SEE NOTE #2 FROM PREVIOUS | | | REVIEW NOT CORRECTED. RISER STILL SHOWS | | | AN EQUIPMENT GROUNDING CONDUCTOR FROM | | | METER TO FIRST MEANS OF DISCONNECT. | | | THIS IS NOT PERMITTED , SEE 250.6,250.24 |
|