2005-03-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) ARCHITECT SHALL PROVIDE THE FOLLOWING
 INFORMATION ON EACH ARCHITECTURAL SHEET.
 A) FIRM NAME, ADDRESS, & PHONE NUMBER.
 FAC 61G1-16.004(1) & FS 481.2055
 2) P, M, & E SHEETS SHOW GEORGE S
 TSENG'S NAME AND PE NUMBER IN THE TITLE
 BLOCK FOR ELMER MARMORSTEIN'S SIGNATURE
 & SEAL. (SEE COMMENT #1)
 3) THE FOLLOWING INFORMATION IS REQUIRED
 ON THE DETAIL FOR THE ACCESSIBLE TOILET
 ROOM:
 A) CLEAR FLOOR SPACE 11-4.16.2
 B) HEIGHT 11-4.16.3
 C) FLUSH CONTROLS 11-4.16.5
 D) 5' TURNING AREA 11-4.22.3
 4) SHT AM-31 A DRINKING FOUNTAIN IS
 REQUIRED PER TABLE 403.1.
 5) SHT PM-31 DOMESTIC WATER RISER
 DIAGRAM:
 A) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE TO MAINT. BUILDING.
 SECTION 608.13.2.
 B) FULL OPEN VALVE IS REQUIRED AT THE
 ENTRANCE TO THE STRUCTURE. SECTION
 606.1(2).
 C) FULL OPEN VALVES ARE REQUIRED ON THE
 TOP OF ALL WATER DOWN-FEED LINES.
 SECTION 606.1(4).
 6) THE OIL SEPARATOR SHALL BE SIZED BY
 RODNEY COMPO, ENVIRONMENTAL COMPLIANCE.
 WASTE ORD. #2938-96. CONTACT MR. COMPO
 (561) 837-4074 ORVIA E-MAIL AT
 [email protected]. - SUBMIT THE WORKSHEET
 FROM MR. COMPO WHEN RESUBMITTING PLANS.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]