| 2005-04-06 00:00:00 | DENIED: | | | 1.PROVIDE INFORMATION AS TO WHAT TYPE | | | OF MAINTENANCE WILL BE DONE ON THE | | | VEHICLES.PER 2001 FBC/M 502.11, AREAS | | | IN WHICH STATIONARY MOTOR VEHICLES ARE | | | OPERATED SHALL BE PROVIDED WITH A SOURCE | | | CAPTURE SYSTEM THAT CONNECTS DIRECTLY TO | | | THE MOTOR VEHICLE EXHAUST SYSTEM. | | | | | | 2.PROVIDE ELEVATION OF THE EF-A, | | | PLEASE NOTE, EXHAUST SHALL BE LOCATED AS | | | NOT TO RECIRCULATE NOXIOUS FUMES BACK | | | INTO THE GARAGE AREA THROUGH THE OPEN | | | GARAGE DOORS. | | | | | | 3.PLEASE SHOW CALCULATION FOR 1.5 | | | CFM/SQ FT. | | | | | | 4.SEE ALSO COMMENT #1 BY DEWEY PALMER | | | ELECTRICAL PLAN REVIEW, REGARDING | | | SIGNATURE & TITLE BLOCK. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|