Plan Review Notes
Plan Review Notes For Permit 05030289
Permit Number 05030289
Review Stop P
Sequence Number 2
Notes
Date Text
2005-07-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA STATUTES
  
 COMMENTS FROM PREVIOUS REVIEW HAVE NOT
 BEEN ADDRESSED.
 1) SHT A-2 DETAIL A. THE FOLLOWING
 INFORMATION REQUIRED FOR THE ACCESSIBLE
 SINK IS NOT SHOWN ON THE DETAIL OR FLOOR
 PLAN:
 A) KNEE CLEARANCE 11-4.24.3
 B) SINK DEPTH 11-4.24.4
 C) CLEAR FLOOR SPACE 11-4.24.5 -
 FORWARD APPROACH REQUIRED, MAXIMUM 19"
 UNDERNEATH THE SINK. CABINET DOORS ARE
 NOT APPROVED PER THE BLDG. OFFICIAL, AS
 THEY SHALL NOT BE IN THE CLEAR FLOOR
 SPACE.
 D) FAUCETS 11-4.24.7
 2) A DRINKING FOUNTAIN IS REQUIRED.
 PLEASE INDICATE IF THERE ARE HI/LOW
 DRINKING FOUNTAINS EXISTING, AND THE
 LOCATION OF DRINKING FOUNTAINS. SECTION
 104.2.1.
 3) SHT P0.1 PLUMBING ISOMETRICS. WATER
 ISOMETRIC, WATER HAMMER ARRESTOR SHALL
 BE LOCATED NEAR THE FIXTURE, IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING AS
 SHOWN. PDI-WH 201. (SEE NOTE #13)
 ****************NEW COMMENTS************
 1B. SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL AND FS553.80(2)B)
 2B. WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE
 ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  