| Plan Review Notes For Permit 05030289 |
| Permit Number |
05030289 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-03-21 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT A-2 DETAIL A. THE FOLLOWING | | | INFORMATION REQUIRED FOR THE ACCESSIBLE | | | SINK IS NOT SHOWN ON THE DETAIL OR FLOOR | | | PLAN: | | | A) KNEE CLEARANCE 11-4.24.3 | | | B) SINK DEPTH 11-4.24.4 | | | C) CLEAR FLOOR SPACE 11-4.24.5 - | | | FORWARD APPROACH REQUIRED, MAXIMUM 19" | | | UNDERNEATH THE SINK. CABINET DOORS ARE | | | NOT APPROVED PER THE BLDG. OFFICIAL, AS | | | THEY SHALL NOT BE IN THE CLEAR FLOOR | | | SPACE. | | | D) FAUCETS 11-4.24.7 | | | 2) A DRINKING FOUNTAIN IS REQUIRED. | | | PLEASE INDICATE IF THERE ARE HI/LOW | | | DRINKING FOUNTAINS EXISTING, AND THE | | | LOCATION OF DRINKING FOUNTAINS. SECTION | | | 104.2.1. | | | 3) SHT P0.1 PLUMBING ISOMETRICS. WATER | | | ISOMETRIC, WATER HAMMER ARRESTOR SHALL | | | BE LOCATED NEAR THE FIXTURE, IN AN | | | "EFFECTIVE RANGE" NOT IN THE CEILING AS | | | SHOWN. PDI-WH 201. (SEE NOTE #13) | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|