| Plan Review Notes For Permit 05030271 |
| Permit Number |
05030271 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2006-05-02 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE DESIGNER OF RECORD MUST PRINT AND | | | SIGN NAME TO SAME, 104.2.1 FBC. | | | | | | 2} CIRCUITS 1&3 @80 AND 22 @ 30 AMPS DO | | | NOT COMPLY WITH 310.16 FOR OCP FOR SIZE | | | OF CONDUCTOR. THESE WERE REDLINED ON THE | | | PREVIOUS PLANS DATED (REVIEWED) 8/1/05. | | | | | | 3} THE MASTER SUITE NEEDS A RECEPTACLE | | | ADDED TO COMPLY WITH 210.52(A)(1). SEE | | | REVIEWED PLAN. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | | | | |
|