Plan Review Notes
Plan Review Notes For Permit 05030271
Permit Number 05030271
Review Stop E
Sequence Number 1
Notes
Date Text
2005-03-17 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} INDICATE THE SIZE OF THE EXISTING
 SERVICE
  
 2} THERE ARE 3 GROUNDING ELECTRODES AT
 THREE DIFFERENT LOCATIONS SHOWN ON THE
 RISER DIAGRAM FOR THE SAME SERVICE WITH
 ALL EQUIPMENT APPARENTLY ON THE SAME
 BUILDING. SHOW GROUNDING SYSTEM PER
 250.50 2002 NEC.
  
 3} SHOW HOW PANELS ARE FED ON THE RISER,
 THE LINES DRAWN TO THE METER DO NOT
 CONNECT TO ANYTHING.
  
 4} INDICATE THE OCP FOR THE PANEL
 FEEDERS. DO THEY HAVE MAIN BREAKERS?
  
 5} 4500 WATTS ON CIRCUIT #4, PANEL "B"
 VIOLATES AMPACITY RATINGS. SEE 310.16.
  
 6} PANEL "A",CIRCUIT #10, SAME AS ABOVE.
  
 7} SEE POOL PUMP CIRCUIT#17 & 19. VERIFY
 THAT THE PUMP HAS #6 WIRE FEEDING A TEN
 AMP PUMP. ALSO NOTE 60 AMP OCP IS TOO
 HIGH TO PROTECT THE PUMP.
  
 8} CIRCUITS # 21 & 23, PANEL "A"
 EXISTING A/C, THE OCP IS TOO LARGE FOR
 THE CONDUCTORS PER 310.16.
  
 9} CIRCUITS # 5 & 7, PANEL "B", SAME
 COMMENT AS #8.
  
 10} SHOW LOCATION OF NEW A/C EQUIPMENT
 ON PLANS .
  
 11} THE FAMILY ROOM MUST HAVE A
 RECEPTACLE ADDED TO COMPLY WITH
 210.52(A). SEE REVIEWED PLAN.
  
 12] THERE MUST BE SMOKE DETECTORS ADDED
 AT THE BOTTOM AND TOP OF THE STAIRWELL
 PER 905.2.2, FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  