| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} INDICATE THE SIZE OF THE EXISTING |
| | SERVICE |
| | |
| | 2} THERE ARE 3 GROUNDING ELECTRODES AT |
| | THREE DIFFERENT LOCATIONS SHOWN ON THE |
| | RISER DIAGRAM FOR THE SAME SERVICE WITH |
| | ALL EQUIPMENT APPARENTLY ON THE SAME |
| | BUILDING. SHOW GROUNDING SYSTEM PER |
| | 250.50 2002 NEC. |
| | |
| | 3} SHOW HOW PANELS ARE FED ON THE RISER, |
| | THE LINES DRAWN TO THE METER DO NOT |
| | CONNECT TO ANYTHING. |
| | |
| | 4} INDICATE THE OCP FOR THE PANEL |
| | FEEDERS. DO THEY HAVE MAIN BREAKERS? |
| | |
| | 5} 4500 WATTS ON CIRCUIT #4, PANEL "B" |
| | VIOLATES AMPACITY RATINGS. SEE 310.16. |
| | |
| | 6} PANEL "A",CIRCUIT #10, SAME AS ABOVE. |
| | |
| | 7} SEE POOL PUMP CIRCUIT#17 & 19. VERIFY |
| | THAT THE PUMP HAS #6 WIRE FEEDING A TEN |
| | AMP PUMP. ALSO NOTE 60 AMP OCP IS TOO |
| | HIGH TO PROTECT THE PUMP. |
| | |
| | 8} CIRCUITS # 21 & 23, PANEL "A" |
| | EXISTING A/C, THE OCP IS TOO LARGE FOR |
| | THE CONDUCTORS PER 310.16. |
| | |
| | 9} CIRCUITS # 5 & 7, PANEL "B", SAME |
| | COMMENT AS #8. |
| | |
| | 10} SHOW LOCATION OF NEW A/C EQUIPMENT |
| | ON PLANS . |
| | |
| | 11} THE FAMILY ROOM MUST HAVE A |
| | RECEPTACLE ADDED TO COMPLY WITH |
| | 210.52(A). SEE REVIEWED PLAN. |
| | |
| | 12] THERE MUST BE SMOKE DETECTORS ADDED |
| | AT THE BOTTOM AND TOP OF THE STAIRWELL |
| | PER 905.2.2, FBC. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |