Notes
Date Text
2006-01-23 00:00:00PLANS REDLINED.
  
  
 PLEASE SEE MIN GEC HAS NOW BEEN CHANGED
 TO A #4.
 THE GEC, SHALL BE SIZED PER 250.66, A #2
 SHALL BE INSTALLED FROM THE FOOTER
 STEEL.
  
 ** ORIG PLANS CALLED FOR 2-COPPER GRNDS
 RODS, 1/0 AWG MIN.
  
  
 250.66,250.64,250.68.