| Plan Review Notes For Permit 05030252 |
| Permit Number |
05030252 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-01-23 00:00:00 | PLANS REDLINED. | | | | | | | | | PLEASE SEE MIN GEC HAS NOW BEEN CHANGED | | | TO A #4. | | | THE GEC, SHALL BE SIZED PER 250.66, A #2 | | | SHALL BE INSTALLED FROM THE FOOTER | | | STEEL. | | | | | | ** ORIG PLANS CALLED FOR 2-COPPER GRNDS | | | RODS, 1/0 AWG MIN. | | | | | | | | | 250.66,250.64,250.68. |
|