2006-04-06 00:00:00*********UNSAT ***********
  
 1) NOTE: PLEASE SEE ALL SHEETS ARE TO BE
 SIGNED, DATED AND SEALED BY THE
 ARCHITECT OF RECORD.
 FS 481.221
  
 2) NOTE: PLEASE SEE MIN GEC HAS NOW BEEN
 CHANGED TO A #4.
 THE GEC, SHALL BE SIZED PER 250.66, A #2
 SHALL BE INSTALLED FROM THE FOOTER
 STEEL.
 ** ORIG PLANS CALLED FOR 2-COPPER GRNDS
 RODS, 1/0 AWG MIN.
 250.66,250.64,250.68.
 PLEASE SEE THE GROUNDING ELECTRODE
 SYSTEMS ON MANY PREVIOUS PLANS HAVE BEEN
 REDLINED, HOWEVER PLANS NEED TO BE
 CORRECTED AT THIS TIME FOR ALL FUTURE
 REVISIONS.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  