| Plan Review Notes For Permit 05030248 |
| Permit Number |
05030248 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-04-06 00:00:00 | *********UNSAT *********** | | | | | | 1) NOTE: PLEASE SEE ALL SHEETS ARE TO BE | | | SIGNED, DATED AND SEALED BY THE | | | ARCHITECT OF RECORD. | | | FS 481.221 | | | | | | 2) NOTE: PLEASE SEE MIN GEC HAS NOW BEEN | | | CHANGED TO A #4. | | | THE GEC, SHALL BE SIZED PER 250.66, A #2 | | | SHALL BE INSTALLED FROM THE FOOTER | | | STEEL. | | | ** ORIG PLANS CALLED FOR 2-COPPER GRNDS | | | RODS, 1/0 AWG MIN. | | | 250.66,250.64,250.68. | | | PLEASE SEE THE GROUNDING ELECTRODE | | | SYSTEMS ON MANY PREVIOUS PLANS HAVE BEEN | | | REDLINED, HOWEVER PLANS NEED TO BE | | | CORRECTED AT THIS TIME FOR ALL FUTURE | | | REVISIONS. | | | | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLANREVIEW | | | 561-805-6717 | | | [email protected] |
|