Plan Review Notes
Plan Review Notes For Permit 05030246
Permit Number 05030246
Review Stop P
Sequence Number 1
Notes
Date Text
2005-03-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 424 SWIMMING POOLS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) ENGINEER SHALL LEGILBLY INDICATE
 THEIR ADDRESS ON EACH SHEET. IF WORKING
 FOR AQUADYNAMICS THAN A CERTIFICATE OF
 AUTHORIZATION REQUIRED BY FAC
 61G15-24.002(2) & FS 471.2055 WILL BE
 REQUIRED IN THE TITLE BLOCK.
 2) SHT SP-1.07 POOL WASTE LINE AIR GAP
 DETAIL AND SWIMMING POOL EQUIPMENT
 PIPING ISOMETRIC DETAIL. THE WASTE LINE
 FROM THE FILTER SHALL BE DRAINED TO
 SANITARY LINE NOT STORM. CITY CODE
 SECTION 90-203(A)
 3) JOINTS AND CONNECTIONS, FBC-2001
 PLUMBING SECTION 605.21, PURPLE PRIMER
 IS REQUIRED ON PVC PIPE AND FITTINGS.
 (ADD TO NOTES).
 4) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 5) PLUMBING SHEETS SHALL NOT BE
 SUBMITTED WITH POOL PLANS - IF THESE ARE
 REVISIONS THEY SHALL BE SUBMITTED AS
 REVISIONS UNDER THE BLD-COM PERMIT
 NUMBER. SECTION 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]