Plan Review Notes
Plan Review Notes For Permit 05030240
Permit Number 05030240
Review Stop E
Sequence Number 1
Notes
Date Text
2005-03-15 00:00:00** UNSAT **
  
 1)NOTE: PLEASE SEE FBC 104.2.1.
 PLANS ARE REQUIRED TO HAVE THE PRINTED
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR PLANS/DESIGN.
  
 2)NOTE: PLEASE SEE 210.52D/210.11C3
 WHICH REQUIRES A DEDICATED BATH CIRCUIT
 FOR GFI/TS ETC. MUST BE 20A #12.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  