Plan Review Notes
Plan Review Notes For Permit 05030231
Permit Number 05030231
Review Stop M
Sequence Number 2
Notes
Date Text
2005-04-18 00:00:00SECOND MECH. PLAN REVIEW.
  
 1. ONLY ONE A/C PLAN AND THEAR NOT
 SIGNED OR SEALED.
 2. A.H.U. IN SECOND FLOOR REQUIRES SAFE
 PAN UNDER UNIT WITH FLOAT SW . 2003
 FBC/M 307.2.3.
 3. MASTER BATH REQUIRE EXHAUST FANS IN
 SHOWER/TUB AREA AND TOILET/BED. ROOM.
 PAT RAFTER 561 805/6728 OR 805/6719
 PATTY KRAUSS
 PLEASE CALL IF THEAR ANY QUESTION.