| Plan Review Notes For Permit 05030231 |
| Permit Number |
05030231 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-04-07 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE LOAD FOR THE SUBPANEL (CIRCUIT | | | #2) @ 16839 WATTS IS TOO LARGE FOR A 60 | | | AMP OCP AND #6 WIRE.16839/240=70 AMPS. | | | | | | 2} WATER HEATER #2@ 4500 WATTS IS NOT | | | SHOWN ON THE PANEL SCHEDULE. | | | | | | | | | 3} THREE BEDROOMS NEED RECEPTACLES ADDED | | | TO COMPLY WITH 210.52 SPACING | | | REQUIREMENTS. SEE REVIEWED PLAN. | | | | | | 4} THE RECEPTACLE FOR THE HOT TUB MUST | | | COMPLY WITH 680.43(A)(3). GFI. | | | | | | 5} ONLY ONE SET OF DRAWINGS WAS SIGNED | | | AND SEALED. SEE 471 FS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|