Plan Review Notes
Plan Review Notes For Permit 05030231
Permit Number 05030231
Review Stop E
Sequence Number 2
Notes
Date Text
2005-04-07 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE LOAD FOR THE SUBPANEL (CIRCUIT
 #2) @ 16839 WATTS IS TOO LARGE FOR A 60
 AMP OCP AND #6 WIRE.16839/240=70 AMPS.
  
 2} WATER HEATER #2@ 4500 WATTS IS NOT
 SHOWN ON THE PANEL SCHEDULE.
  
  
 3} THREE BEDROOMS NEED RECEPTACLES ADDED
 TO COMPLY WITH 210.52 SPACING
 REQUIREMENTS. SEE REVIEWED PLAN.
  
 4} THE RECEPTACLE FOR THE HOT TUB MUST
 COMPLY WITH 680.43(A)(3). GFI.
  
 5} ONLY ONE SET OF DRAWINGS WAS SIGNED
 AND SEALED. SEE 471 FS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  