Plan Review Notes
Plan Review Notes For Permit 05030231
Permit Number 05030231
Review Stop P
Sequence Number 1
Notes
Date Text
2005-03-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1)SHT SP1 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS. SEE RED LINE
 CORRECTIONS ON ONE SET OF PLANS.
 A) ALL SHOWERS, TUBS, AND THE BIDET
 SHALL BE TRAPPED. SECTION 1002.1
 B) KITCHEN SINK IS AN ISLAND SINK AND AS
 SUCH CAN NOT BE VENTED AS SHOWS. EITHER
 AN ISLAND VENT OR AN AIR ADMITTENCE
 VALVE IS SUGGESTED. SECTION 901.2.1.
 C) FITTINGS SHALL BE INSTALLED TO GUIDE
 SEWAGE AND WASTE IN THE DIRECTION OF
 FLOW. FITTING UPSTREAM OF THE WASH
 MACHINE WITH THE CLEANOUT DOES NOT
 COMPLY. SECTION 706.3.
 D) FITTING, (TEE), AT THE TOP OF THE
 RISER TO THE SECOND FLOOR IS NOT
 APPROVED PER SECTION 706.3. USE A WYE
 FITTING TO CONNECT M/B AND SWEEP (90) TO
 CONNECT OTHER BATHROOMS AS SHOWN.
 2) ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS, AND LICENSE NUMBER
 ON EACH SHEET. 61G15-23.002(2) AND FS
 471.025.
 3) THE GARRISON DESIGN GROUP TITLE BLOCK
 SHALL CONTAIN, AT A MINIMUM, THE
 FOLLOWING INFORMATION:
 FIRM LICENSE NUMBER & CERTIFICATE OF
 AUTHROIZATION. FAC 61G1-16.004(2) AND FS
 481.219 - FS 481.2055 - THIS IS REQUIRED
 ON EACH SHEET
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]