| Plan Review Notes For Permit 05030175 |
| Permit Number |
05030175 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-03-21 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT A1 DETAIL #6 FOLLOWING | | | INFORMATION IS REQUIRED ON DETAIL: | | | A) KNEE CLEARANCE 11-4.24.3 (HEIGHT) | | | B) CLEAR FLOOR SPACE 11-4.24.5FORWARD | | | APPROACH REQUIRED, MAX. 19" UNDERNEATH | | | THE SINK. - PER BUILDING OFFICIAL, NO | | | DOORS IN CLEAR FLOOR SPACE UNDER SINK. | | | C) EXPOSED PIPES AND SURFACES 11-4.24.6 | | | | | | 2) PLEASE INDICATE IF DRINKING FOUNTAINS | | | ARE AVAILABLE IN THE COMMON AREAS OF THE | | | BUILDING. | | | | | | 3) A FULL OPEN VALVE IS REQUIRED ON ALL | | | WATER DOWN-FEED LINES. SECTION 606.1(4) | | | | | | 4) SHOW WATER HAMMER ARRESTOR REQUIRED | | | BY SECTION 604.9 ON WATER RISER DIAGRAM. | | | SECTION 104.2.1. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|