| 2005-03-14 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} CALCULATE AND SUBMIT THE AVAILABLE | | | FAULT CURRENT AND INDICATE AIC RATING | | | FOR THE SERVICE EQUIPMENT PER 110.9 & | | | 10. | | | | | | 2} THE RISER DIAGRAM IS TO VAGUE. | | | INDICATE WHAT IS TO BE INSTALLED ON THE | | | PLAN. REMOVE ALL "OPTIONS" AND "IF | | | REQUIRED" LANGUAGE. IF UNCERTAIN | | | COORDINATE WITH ELECTRICAL CONTRACTOR. | | | | | | 3} INDICATE THE LOCATION OF ALL SERVICE | | | EQUIPMENT ON THE PLAN PER 110.26, 215.5 | | | AND 230.70 CWBP AMMENDMENTS. | | | | | | 4} INDICATE ALL COMPONENTS OF THE | | | GROUNDING ELECTRODE SYSTEM PER 250.50. | | | | | | 5} CORRELATE THE MECHANICAL SPECS AND | | | ELECTRICAL PANEL FOR EQUIPMENT SIZE. SEE | | | AHU HEATER SIZE. | | | | | | 6} INDICATE COMPLIANCE OF 210.12 AFCI | | | FOR SLEEPING ROOMS ON PANEL SCHEDULE. | | | | | | 7} THE ENGINEER OF RECORD MUST PROVIDE A | | | TITLE BLOCK ON THE PLANS PER FAC | | | 61G15-23.002. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|