| 2005-03-18 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT. |
| | |
| | 2- IMPACT FEES RECEIPT SHOWS A BALANCE |
| | DUE. PAY BALANCE AND BRING BACK COPY OF |
| | RECEIPT PAID IN FULL. |
| | |
| | 3- ENGINEER NEEDS TO HAVE ALL HIS |
| | INFORMATION AS REQUIRED BY CHAPTER 471 |
| | FL.STATUTES. ALSO, SEE ADMINISTRATIVE |
| | CODE SECTION 61G15-23.002 FOR |
| | INFORMATION REQUIRED BY ENGINEER. |
| | |
| | 4- NEED TO PROVIDE 2 SETS OF PLANS AND |
| | ALL REQUIRED INFORMATION. |
| | |
| | 5- SPECIFY 30PSF OR 10PSF ATTIC LIVE |
| | LOAD AS REQ'D BY TABLE 1604.1 FBC 2001. |
| | |
| | 6- SPECIFY WHAT'S THE USE OF THE ROOM |
| | ADJACENT TO THE KITCHEN. |
| | |
| | 7- REVISE TYPICAL WALL SECTION TO SHOW |
| | FOOTING TO BE 12" MIN. BELOW GRADE (SEC. |
| | 1804.1.3 FBC 2001) AND CONCRETE SLAB TO |
| | BE MIN. 4" ABOVE FINISH GRADE AS REQ'D |
| | BY SEC. 1804.1.7 CITY AMENDMENTS TO FBC. |
| | |
| | 8- PROVIDE SOIL TEST REPORT. |
| | |
| | 9- CLARIFY FOOTING REINFORCEMENT. TYP. |
| | WALL SECTION CALLS FOR 3#5, WHILE |
| | FOUNDATION PLAN CALLS FOR 2#5. REVISE. |
| | |
| | 10- SPECIFY CEILING INSTALLATION AT |
| | ENTRY PORCH. SPECIFY FASTENERS SIZE AND |
| | SPACING. SEE ASTM C926 AND ASTM C1063. |
| | SEC. 2504.2 FBC 2001. |
| | |
| | 11- PROVIDE CLEAR TRUSS ANCHOR SCHEDULE. |
| | SEC. 104.2.1.2 CITY AMENDMETNS TO FBC |
| | 2001. (SEE LATEST SIMPSON CATALOGUE AND |
| | PROVIDE ENGINEERING FOR TYPE AND NUMBER |
| | OF FASTENERS THAT DIFFER FROM |
| | CATALOGUE). SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 12- TRUSS NOTES ON SHEET A-3 AND TYP |
| | WALL SECTION DON'T MATCH. SEE TYPE AND |
| | NUMBER OF FASTENERS SPECIFIED AND REVISE |
| | AS REQUIRED. |
| | **NOTE: SEE LATEST SIMPSON CATALOGUE FOR |
| | NUMBER OF FASTENERS TO BE USED. |
| | FASTENERS WERE REVISED TO COMPLY WITH |
| | SEC. 1609.4.3 FBC 2001 WERE THE STEEL |
| | STRESS COULD NOT BE INCREASED. |
| | OTHERWISE, ENGINEER TO PROVIDE |
| | ENGINEERING CALCULATIONS (SEE SEC. |
| | 1609.4.3 FBC 2001)FOR NUMBER OF |
| | FASTENERS THAT DIFFER FROM THOSE TESTED |
| | AND PUBLISHED BY MANUFACTURER. |
| | |
| | 13- LINTEL SCHEDULE DON'T MATCH PLAN. |
| | REVISE AS REQUIRED. |
| | |
| | 14- ENERGY CALCULATIONS: A) OWNER/AGENT |
| | TO SIGN AND DATE BOTTOM OF FORM. |
| | B) COMPLETE INFORMATION ON TOP OF FORM. |
| | INCLUDING BUILDING ADDRESS. |
| | |
| | 15- STORM SHUTTERS: A) PROVIDE FLORIDA |
| | OR LOCAL PRODUCT APPROVAL. |
| | B) PROVIDE KEY PLAN AND COMPLETE |
| | INSTALLATION SCHEDULE. SEE SAMPLE. |
| | C) CLEARLY MARK ON SHUTTER DRAWINGS |
| | SPECIFIC MOUNTING CONDITIONS AND ANCHOR |
| | TYPE AND SPACING TO BE USED ACCORDING TO |
| | THE DESIGN PRESSURES, EDGE DISTANCE, |
| | PANEL SPAN, CONNECTION TYPE AND |
| | STRUCTURE TO BE ATTACHED TO (MASONRY OR |
| | CONCRETE). |
| | |
| | 16- PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR: (NOTE: DADE COUNTY PRODUCT |
| | APPROVAL IS NOT A FLORIDA PRODUCT |
| | APPROVAL) |
| | A) WINDOW MULLIONS. |
| | B) SLIDING GLASS DOORS AND CLEARLY |
| | IDENTIFY SIZE OF SILL TO BE USED |
| | ACCORDING TO THE DESIGN PRESSURES. |
| | C) GARAGE DOOR FOR SIZE OF DOOR USED. |
| | D) ROOF SHINGLES. |
| | E) ENTRY DOOR.NOTE: INSWING AS SHOWN |
| | ON PLANS. |
| | F) SIMPSON TRUSS CONNECTOR USED. |
| | G) SINGLE HUNG WINDOWS. |
| | |
| | 17- DESIGN PRESSURES SPECIFIED FOR |
| | GARAGE DOOR ARE TOO LOW. PROVIDE |
| | ENGINERING CALCULATIONS SHOWING HOW THE |
| | DESIGN PRESSURES WERE DETERMINED. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | |
| | 18- OWES $116.20 FOR LOW VALUATION AND |
| | RADON FEES. |
| | |
| | 19- CLARIFY R VALUE FOR INSULATION AT |
| | ATTIC. ENERGY CALCS CALLS FOR R-19, |
| | WHILE TYP. WALL SECTION CALLS FOR R-30. |
| | REVISE AS REQUIRED. |
| | |
| | 20- SHEET A-3: A) CLARIFY FASTENER FOR |
| | GARAGE DOOR BUCK. NOTES ON SHEET A-1 AND |
| | NOTES ON DETAIL DON'T MATCH. REVISE. |
| | B) CLARIFY CONNECTORS SPECIFIED FOR |
| | ENTRY PORCH BEAM. WHAT'S HUS210-3? SEE |
| | SIMPSON CATALOGUE. |
| | C) SPECIFY THE 4 STRAPS SPECIFIED FOR |
| | ENTRY PORCH ON TOP OF CONCRETE COLUMN. |
| | NOTE: NEED WOOD TO MASONRY CONNECTOR. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | D) ROOF FRAMING PLAN IS MISSING LINTEL |
| | AT ROOM ADJACENT TO KITCHEN. |
| | SEE COMMENTS ON PLANS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |