| Plan Review Notes For Permit 05030144 |
| Permit Number |
05030144 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-03-07 00:00:00 | ***UNSAT *** | | | | | | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON | | | PLANS AND CORRELATE WITH A SUBMITTED | | | PANEL SCHEDULE. | | | 215.5 | | | PLEASE ALSO SEE 700.12E FOR CIRCUITING | | | OF ANY EM/EXT LTS. | | | | | | 2)NOTE: PLEASE SHOW NEW OR EXSITNG SIGN | | | CIRCUIT REQUIRED UNDER 600.5 | | | | | | 3)NOTE: PLEASE PROVIDE OCCUPANCY/LOAD | | | FOR NEW ELECTRICAL ON EXISTING PANEL | | | SHOWN. | | | 215.5,220 | | | | | | PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER REVIEWER(S) WHICH MAY OR MAY NOT | | | AFFECT ELECTRICAL PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|