2005-03-07 00:00:00***UNSAT ***
  
 1)NOTE: PLEASE PROVIDE LAYOUT OF EITHER
 NEW OR EXISTING REQUIRED GFI RECEPTS PER
 210.52C1-5.
 PLEASE ALSO SEE 210.8A6
  
 2)NOTE: PLEASE PROVIDE ADDRESS/AND UNIT
 # ON PLANS.
 FAC 61G1-16
 PLEASE ALSO PROVIDE THE PRINTED NAME OF
 THE PERSON RESPONSIBLE FOR PLANS.
 FBC 104.2.1
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  