| Date |
Text |
| 2006-12-27 17:46:31 | *** UNSAT ** |
| | |
| | 1) NOTE: PLEASE SUBMIT ONE COMPLETE SET OF |
| | PHOTO-METRICS. PLEASE KNOW AS THIS IS REQUIRED UNDER |
| | THE ELECTRICAL, LIFE SAFETY AND ELECTRICAL ENGINEER IS |
| | ALSO RESPONSIBLE FOR THIS SCOPE OF WORK, ALL PLANS |
| | SHALL BE DONE BY THE ENGINEER OF RECORD. FS 471.025 |
| | PLEASE SEE SOME PHOTO-METRICS WERE DONE BY THE ENGINEER |
| | HOWEVER THEY ARE NOT THE SAME AS THE OTHERS DONE WHICH |
| | WERE NOT SIGNED, AND SEALED BY ANYONE. |
| | PLEASE KNOW AS PER NFPA-101, 7.9, AND 7.8, 7.8.1.3, |
| | 7.9.2.2, EMERGENCY LIGHTING IS REQUIRED OUT OF THE |
| | BUILDING LEADING TO THE PUBLIC RIGHT OF WAY. PLEASE SEE |
| | THIS WOULD INCLUDE STAIRS OUTSIDE. |
| | PLEASE SEE ONE OF THE MOST IMPORTANT ITEMS WAS REMOVED |
| | FROM PLANS WHICH WERE THE REQUIRED BATTERY BACK UP |
| | FIXTURES FROM THE STAIRWAYS. PLEASE SEE THAT SOME SORT |
| | OF BATTERY BACK UP FIXTURES WILL BE REQUIRED AS |
| | REQUIRED AND SHOWN ON ORIGINAL PLANS. |
| | |
| | 2) NOTE: PLEASE SEE THE NEW PROPOSED SERVICE FOR THE |
| | CHPP IS NOT YET APPROVED AS SHOWN. PLEASE SEE 230.2 |
| | WHICH SPECIAL PERMISSION MUST FIRST BE GRANTED BY THE |
| | AHJ IF THE BUILDING MEETS THE EXCEPTIONS TO INSTALL NEW |
| | SERVICE. PLEASE KNOW AT THIS TIME THIS IS NOT |
| | PERMITTED. |
| | PLEASE SEE CHILLER PLANT STRUCTURE/AREA/BUILDING |
| | CONTAINS A FEEDER FROM THE OTHER ELECTRICAL SERVICE |
| | WHICH ISNOT PERMITTED AND/OR IF IT DOES COMES TO THE |
| | POINT OF BEING PERMITTED, THEN A MEANS OF DISCONNECT |
| | AND SIGNAGE AT THIS LOCATION FOR PANEL AUX WILL BE |
| | REQUIRED AT A MINIMUM. |
| | 225.31-225.39, 230.2E ETC. |
| | |
| | 3) NOTE: PLEASE SEE AS NOTED ABOVE IN NOTE #2, PLEASE |
| | EXPLAIN AND INDICATE ANY CONTROL WIRING OR CONDUCTORS |
| | OF ANY TYPE WHICH ARE BEING INSTALLED FROM THE NEW |
| | PROPOSED CHILLER PLANT SERVICE WHICH WILL PROCEED INTO |
| | THE MAIN COURTHOUSE BUILDING WHICH IS BEING FED FROM A |
| | COMPLETELY DIFFERENT SERVICE AND SEPARATE FPL |
| | TRANSFORMER. |
| | PLEASE SEE MIXING OF SERVICES AND MEANS OF DISCONNECTS |
| | REQUIRED FOR THESE CONDUCTORS OR CONTROL WIRING PER |
| | 225.31-225.39. |
| | PLEASE KNOW AS MUCH OF NOTES 2 AND 3 ARE NOT KNOWN AT |
| | THIS TIME, THERE MAY BE COMMENTS WHICH WILL FOLLOW THIS |
| | REVIEW. |
| | |
| | 4) NOTE: PLEASE SEE 240.4C WITH RESPECT TO THE MINIMUM |
| | SIZE OF THE SERVICE ENTRANCE CONDUCTORS AS WELL AS THE |
| | MINIMUM SIZE FOR FEEDERS FOR DEVICES RATED OVER 800A?S. |
| | PLEASE SEE SECTIONS AS THESE SHALL BE SIZED AT OR ABOVE |
| | THE MINIMUM RATING OF THE OVER CURRENT PROTECTION |
| | DEVICE. PLEASE SEE 310.16, 110.14. |
| | PLEASE CORRELATE AND ADJUST. |
| | PLEASE SEE THIS IS FOR ALL DEVICES OVER 800A ARE, |
| | INCLUDING ALL MAINS ON BUILDING. IF THE CONDUCTORS TO |
| | MAINS ARE BY UTILITY COMPANY THIS WOULD NOT APPLY. |
| | |
| | 5) NOTE: PLEASE SUBMIT MANUFACTURE?S SPECS/CUT SHEETS |
| | FOR THE NEW TANK LESS WATER HEATERS/INST-HOT UNITS. |
| | 110.3, 90.7. |
| | |
| | |
| | 6) NOTE: PLEASE SEE MISSING FOOTER STEEL FOR CHILLER |
| | PLANT AREAS PER 250.32, 2500.50. |
| | |
| | 7) NOTE: PLEASE SEE THERE ARE SEVERAL AREAS ON PLANS |
| | WHICH INDICATE A REV #3, ALTHOUGH NOTHING HAS CHANGED |
| | FROM THE PREVIOUS/ORIGINAL SET OF PLANS WHICH CONTAIN |
| | THE SAME ITEMS, WORDING ETC. |
| | PLEASE SEE JUST TO NAME A FEW, NOTES ON RISER SHEETS |
| | #3, NOTES #16-21 ETC. |
| | RISER FOR MAINS? ETC |
| | PLEASE EXPLAIN REVISION AND WHAT IS BEING REVISED SINCE |
| | REVISION #2, AS PLANS ARE NOT CHANGED FROM FILE/RECORD |
| | SET OF PLANS. |
| | FBC 106.1.2 ADMIN SECTION. |
| | |
| | 8) NOTE: PLEASE SEE ALSO SEE NOTE ABOVE WITH RESPECT TO |
| | LOCATION ON PLANS NOTED FOR REVISION #1, YET CHANGES |
| | COULD NOT BE FOUND FROM RECORD SET OF PLANS? |
| | |
| | 9) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPEOF |
| | WORK ON PROJECT NEEDS TO BE UPDATED AS THE SCOPE OF |
| | WORK FOR MANY ITEMS HAS COMPLETELY CHANGED FROM APPLIED |
| | AMOUNT. |
| | PLEASE SEE PREVIOUS FBC ADMIN SECTION 106.3.5 OR |
| | CURRENT CODE 108.3 BOTH OF WHICH STATE THE SAME |
| | REQUIREMENTS. |
| | THIS IS REQUIRED BEFORE ANY FURTHER REVISIONS ARE DONE |
| | AND VALUE WILL BE REVIEWED FOR PROJECT. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |