| Plan Review Notes For Permit 05030119 |
| Permit Number |
05030119 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2006-09-25 00:00:00 | ----------------PROVISO----------------- | | | 1.PAGE M202:PROVIDE LOUVER AND PLENUM | | | SIZE INFORMATION FOR 12X10 EXHAUST DUCT | | | UP FROM 1ST FLOOR TO EXTERIOR WALL. | | | | | | 2.PAGE M204: E.F.1 ON ROOF TO COMPLY | | | WITH FBC,M 304.8 AND 306.5.A GUARD | | | WILL BE REQUIRED ON ROOF IF FAN IS | | | WITHIN 10' OF ROOF EDGE. | | | | | | RONALD J REGUEIRO | | | 561.805.6734 |
|