| 2006-10-28 20:19:45 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6652 |
| | E-MAIL: [email protected] |
| | |
| | SUBMITTAL ON 10/10/06 FOR EXIT STAIR DOORS: 90 MINUTE |
| | CUSTOM DOORS WITH TRANSOMS AND SIDELIGHTS. |
| | |
| | 1)THE SUBMITTED LETTER DATED 10/6/06 STATES THAT THE |
| | TRANSOM AND SIDELIGHTS PANELS WILL BE BUILT AS THE U.L. |
| | TESTED DOOR LEAF, BUT NO SHOP DRAWINGS, FOR THE TESTED |
| | DOOR LEAF OR THE UNTESTED TRANSOM/SIDELIGHT PANELS, |
| | WERE SUBMITTED FOR REVIEW. |
| | |
| | 2) THE DOOR ELEVATIONS SHOW THAT THE 1ST FLOOR DOORS |
| | WILL BE ALL WOOD AND THE 2ND AND 3RD FLOOR DOORS WILL |
| | EACH BE WOOD LOWER PANEL AND GLASS UPPER PANEL.SO, |
| | THE COMPOSITION OF THE U.L. TESTED DOORS WILL BE |
| | SIGNIFICANTLY DIFFERENT TO THE TRANSOM AND SIDELIGHTS, |
| | CONSIDERING THAT THE FRAME ELEVATIONS, FOR 2ND AND 3RD |
| | FLOOR, SHOW TRANSOM AND SIDELIGHTS WHICH ARE |
| | PREDOMINANTLY GLASS AND THUS DIFFERENT FROM THE U.L. |
| | TESTED DOORS.ALSO, THE SUBMITTED 'FIRELITE PLUS' |
| | TECHNICAL DATA SHEET STATES THAT, FOR A 90 MINUTE |
| | RATING, THE GLASS IN THE TRANSOM/SIDELIGHT SHALL NOT |
| | EXCEED A MAXIMUM WIDTH/HEIGHT OF 56.5" (OR 58.5"- |
| | SUBMITTED COPY IS NOT CLEARLY LEGIBLE).THE FRAME |
| | ELEVATIONS, FOR 2ND AND 3RD FLOOR, SHOW TRANSOM AND |
| | SIDELIGHTS WHICH APPEAR TO EXCEED THAT DIMENSION IN |
| | EITHER WIDTH OR HEIGHT. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |