| 2005-07-15 00:00:00 | DENIED: 2ND REQUEST |
| | REFERENCE PREVIOUS REVIEW DATED 4-6-05 |
| | |
| | COMMENT #1 A: PLEASE ANNOTATE ON PLANS |
| | WHERE PENETRATIONS COMPLY WITH THE |
| | CRITERIA LISTED IN 2001 FBC/M 607.1.3, |
| | EXCEPTION #3 ITEMS 1 THROUGH 4. |
| | |
| | COMMENT #2:WALL TYPE 14 IS NOT |
| | INDICATED ON PLAN SHEET A7.01, STORAGE |
| | RM #214, ARCHITECTURAL PLAN INDICATE |
| | EXISTING OPENING TO BE "PATCHED OR |
| | CLOSED" IN WHICH THE "NEW" PART OF THE |
| | WALL HAS A 1 HR RATING.PLEASE CLARIFY. |
| | PLEASE NOTE, AIR IS TRANSFERRED FROM THE |
| | STORAGE RM #214 BACK THE THE MECH |
| | CLOSET, NO COMBUSTIBLES ARE TO BE STORED |
| | IN THE |
| | COMMENT #5: LIFE SAFTEY PLAN INDICATES 2 |
| | HR RATING FOR THE "OPEN" AREA ON THE 4TH |
| | FOR.SIDE WALL GRILLES DO NOT INDICATE |
| | FIRE DAMPERS.PLEASE CLARIFY. |
| | |
| | COMMENT #6:PLAN SHEET C2 STILL |
| | INDICATES A/C CONDENSATE INTO THE |
| | SANITARY WHICH IS PROHIBITED BY THE CITY |
| | CODE SEC. 90-125 (5). |
| | |
| | COMMENT #7:PLEASE CORRELATE THE LIFE |
| | SAFETY & ARCHITRUAL PLANS. |
| | ARCHITECTURAL PLANS INDICATE RATED WALLS |
| | WEREAS THE THE LIFE SAFETY PLANS DO NOT |
| | INDICATE RATING. |